Abstract
This paper, which consists of two parts, dealt with the parameter tuning of the power system stabilizer for a 612[MVA] thermal power plant in KEPCO system and its validation in field test. In Part 1 of the paper, the selection of parameters such as lead-lag time constants for phase compensation, system gain was optimized by using linear & eigenvalue analyses and they were verified through the time-domain transient stability analysis. In part 2, the performance of PSS was finally verified by the generator's on-line field test. Through the comparisons of simulation results and measured data before and after tuning of the PSS, the models of generator and its controllers including AVR, Governor and PSS used in the simulation are validated and confirmed.
본 논문에서는 전력계통에서 발생하는 저주파 진동을 억제하여 계통에 댐핑력을 제공함으로써 계통 안정도를 향상시킬 수 있는 전력계통 안정화장치의 정수선정 기법과 현장시험을 통한 성능검증 방법을 제시하였다. 대상 발전기는 우리나라 계통에 설치되어 있는 612[MVA]급 화력발전기이며, 축 속도를 입력으로 하는 아날로그 전력계통 안정화장치를 적용대상으로 하였다. 본 논문에서는 먼저, 오프라인에서 선형 해석 및 고유치 해석을 통하여 최적정수를 선정하는 기법을 제시하고, 시간영역 과도 안정도 해석을 이용하여 선정된 정수를 검증하였다(Part I). 또한, 선정된 전력계통 안정화장치의 성능을 온라인 현장시험을 통하여 최종적으로 검증하였으며, 정수선정 전 후의 오프라인 시뮬레이션 결과와 온라인 시험결과를 비교 분석함으로써, 결정된 모델의 적정성을 확인하였다(Part II). 이를 통하여, 축 속도를 입력으로 하는 PSS의 정수선정 방법과 실 계통 현장시험을 통한 성능검증 방법을 제시하였다.