A Special Protection Scheme Against a Local Low-Voltage Problem and Zone 3 Protection in the KEPCO System

  • Yun, Ki-Seob (South Seoul Power Transmission Center, Korea Electric Power Corporation) ;
  • Lee, Byong-Jun (Advanced Power Systems Research Center(APSRC), Korea University) ;
  • Song, Hwa-Chang (School of Electronic and Information Engineering, Kunsan National University)
  • Published : 2007.09.01

Abstract

This paper presents a special protection scheme, which was established in the KEPCO (Korea Electric Power Corporation) system, against a critically low voltage profile in a part of the system after a double-circuit tower outage. Without establishing the scheme, the outage triggers the operation of a zone 3 relay and trips the component. This sequence of events possibly leads to a blackout of the local system. The scheme consists of an inter-substation communication network using PITR (Protective Integrated Transmitter and Receiver) for acquisition of the substations' data, and under-voltage load shedding devices. This paper describes the procedure for determining the load shedding in the scheme and the experiences of the implementation.

Keywords

References

  1. C. W. Taylor, Power System Voltage Stability, McGraw-Hill, 1994
  2. P. Kundur, Power System Stability and Control, McGraw-Hill, 1994
  3. M. Jonsson and J. E. Daalder, 'An adaptive scheme to prevent undesirable distance protection operation during voltage instability,' IEEE Trans. on Power Delivery, vol. 18, no. 4, Oct. 2003, pp. 1174-1180 https://doi.org/10.1109/TPWRD.2003.817501
  4. H. Song, B. Lee, and V. Ajjarapu, 'Determination of control strategies against undesired protective operation with respect to voltage collapse,' Bulk power system dynamics and control - VI, Cortian d'Ampezzo, Italy, Aug. 22-27, 2004
  5. D. Karlsson and X. Waymel, Eds., System protection schemes in power networks, Rep., CIGRE Task Force 38.02.19, June 2001
  6. C. W. Taylor, 'Concepts of undervoltage load shedding for voltage stability,' IEEE Trans. Power Systems, vol. 7, no. 2, April 1992, pp. 480-488
  7. C. Moors, D. Lefebvre, and T. Van Cutsem, 'Design of load shedding schemes against voltage instability,' in Proc. of 2002 IEEE PES Winter Meeting
  8. D. Karlsson, Eds., Protection against voltage collapse Rep., CIGRE Tast Force 34.08, 1998
  9. F. Dobraca, M. A. Pai, and P. W. Sauer, 'Relay margins as a tool for dynamical security analysis,' International Journal of Electrical Power & Energy Systems, vol. 12, no. 4, Oct. 1990, pp. 226-234 https://doi.org/10.1016/0142-0615(90)90038-D

Cited by

  1. A Study on Setting SPS for Generator Tripping Action considering Operating Conditions of Power Systems vol.15, pp.1, 2014, https://doi.org/10.5762/KAIS.2014.15.1.411