Condensation Heat Transfer Characteristics of R-410A as an Alternative R-22 in the Condenser with Small Diameter Tubes
세관을 사용한 응축기에서 R-22의 대체냉매인 R-410A의 응축 열전달 특성
- Son, Chang-Hyo (School of Mechanical Engineering, Pukyong National University)
- 손창효 (부경대학교 기계공학부)
- Published : 2007.06.30
Abstract
An experimental study to investigate the condensing heat transfer characteristics of small diameter horizontal double pipe heat exchangers with R-22 and R-410A was performed. Experimental facility was constructed to calculate and observe HTC(heat transfer coefficients), flow patterns and pressure drop. The main components include a liquid pump, an evaporator, a condenser(test section), a sight-glass, pressure taps and measurement apparatus. Two pipes of different diameters are tested; One 5.35 mm ID 0.5 mm thick, the other 3.36 mm ID 0.7 mm thick. The mass flow rate ranged from 200 to
프레온계 냉매의 지구온난화와 오존층파괴 문제로 인해 대체냉매로서 R-410A가 주목을 받고 있다. 이러한 대체냉매를 세관에 적용시킬 경우 효율을 향상시킬 뿐만 아니라 지구환경에 미치는 영향을 감소시키고, 대기를 청정하게 만드는 기술 및 방안으로 각광 받고 있다. 따라서 본 연구에서는 R-22의 대체냉매로 각광받고 있는 R-410A의 세관응축기 내에서의 응축열전달 특성에 대해 실험적으로 고찰하고자 하였다. 실험장치는 유동양식, 열전달, 압력강하 특성을 파악할 수 있도록 제작되었고, 주요 구성품은 냉매펌프, 증발기, 응축기(시험부), 사이트 글라스(가시화부), 압력탭, 측정장치 등이다. 시험부의 내관은 내경 3.36 mm와 5.35 mm인 수평평활 동관이다. 실험변수들의 범위로서 질량유속