Field Studies on the Improvement of Indoor Air Quality by Ventilator in Apartment Houses

공동주택용 환기장치의 실내공기질 개선효과에 대한 현장실험연구

  • Sung, Ki-Chul (Institute of Construction Technology, Daewoo Engineering & Construction) ;
  • Chang, Hyun-Jae (Institute of Construction Technology, Daewoo Engineering & Construction)
  • 성기철 ((주)대우건설 기술연구원 건축연구팀) ;
  • 장현재 ((주)대우건설 기술연구원 건축연구팀)
  • Published : 2007.02.10

Abstract

Ventilation system is being recommended as an effective tool to improve indoor air quality (IAQ) in apartment houses. Recently, in Korea, apartment house suppliers must establish ventilation system in apartment houses in law. In this study, improvement of IAQ by establishing mechanical ventilation system at apartment house was investigated by mockup test. Seven apartment houses were arranged for the test and improvement of IAQ was examined under the various conditions of ventilation rates, ventilator type and duct works. The results of this study show that IAQ in the test houses which were established mechanical ventilation system was improved about from 30% to 40% compared with IAQ in the apartment house which was not established ventilation system. However, there were no apparent concentration differences between the cases of changing ventilation rates, ventilator types and ductworks.

Keywords

References

  1. Lee, J. J., Lee, J. H. and Lee, S. M., 2005, IAQ field survey in an apartment housing equipped for heat recovery ventilation system with air cleaning function, Korean Journal of Air-Conditioning and Refrigeration Engineering, Vol. 17, No.6, pp.688-693
  2. Ying, Y. U., 2000 The conversion of formaldehyde concentration according to the change of temperature and humidity, Seminaries of Technical Papers of Annual Meeting Architectural Institute of Japan
  3. Study on the determination of standards test method for indoor air quality, Korea Institute of Construction Technology, 2004. 2
  4. KS B 6879 Heat recovery ventilators, Korean Standards Association, 2003. 12. 30
  5. Indoor air quality official test method, Ministry of Environment, 2004. 6
  6. Indoor air quality management method of the multiplex facilities, Ministry of Environment, 2004. 5
  7. The rule about equipment standards of buildings, Ministry of Construction & Transportation, 2006. 2