초록
This paper describes the methods for the detection of shorted-turn in the rotor of a cylindrical synchronous generator. A search coil is installed in the air-gap to detect the shorted-turn. The occurrence of a fault in the rotor winding results in a decrease of the induced voltages in the stator. And the magnitude of the rotor flux can be estimated by using the search coil and the estimated stator voltages respectively. And the magnitude of the estimated rotor flux is used for discriminating the rotor windings short or not by detecting the magnitude of the rotor flux. The method using a search coil located in the air-gap can detect not only the occurrence of a turn fault but also its position in the rotor winding. But the method using the estimated stator voltages gives the magnitude of the rotor flux, and only the number of a short-turn.