초록
This paper proposes the architecture and protocol of a data communication network for the safety system in nuclear power plants. First, we establish four design criteria with respect to determinability, reliability, separation and isolation, and verification/validation. Next we construct the architecture of the safety network for the following systems: PPS (Plant Protection System), ESF-CCS (Engineered Safety Features-Component Control System) and CPCS (Core Protection Calculator System). The safety network consists of 12 sub-networks and takes the form of a hierarchical star. Among 163 communication nodes are about 1600 origin-destination (OD) pairs created on their traffic demands. The OD pairs are allowed to exchange data only during the pre-assigned time slots. Finally, the communication protocol is designed in consideration of design factors for the safety network. The design factors include a network topology of star, fiber-optic transmission media, synchronous data transfer mode, point-to-point link configuration, and a periodic transmission schedule etc. The resulting protocol is the modification of IEEE 802.15.4 (LR-WPAN) MAC combined with IEEE 802.3 (Fast Ethernet) PHY. The MAC layer of IEEE 802.15.4 is simplified by eliminating some unnecessary (unctions. Most importantly, the optional TDMA-like scheme called the guaranteed time slot (GTS) is changed to be mandatory to guarantee the periodic data transfer. The proposed protocol is formally specified using the SDL. By performing simulations and validations using Telelogic Tau SDL Suite, we find that the proposed safety protocol fits well with the characteristics and the requirements of the safety system in nuclear power plants.