The Study on the Decrease of Pressure of Low-rise Building using Circle Porosity Fence

원형방풍팬스를 이용한 저층건물의 풍압저감을 위한 연구

  • 전종길 (전주공업대학 건축과) ;
  • 김성현 (전북대학교 건축.도시공학과) ;
  • 유장열 (전북대학교 건축.도시공학과) ;
  • 유기표 (전북대학교 건축.도시공학과) ;
  • 김영문 (전북대학교 건축.도시공학과)
  • Published : 2006.03.15

Abstract

The effects of porous wind fence on the pressure characteristics around low-rise building model were investigated experimentally. Flow characteristics of velocities and turbulences behind wind fence were measured using hot-wire anemometer The wind fence characterize by varying the porosity of 0%, 20% and the distances from the wind fence from 1H to 9H with maintaining the uniform flow velocity of 6 m/s. we investigated the overall characterization of the low-rise building by measuring pressure seventy four on model. The effects of porosity fences varied with the porosity of the fence and measurement locations(1H-9H). The 20% porosity proved to be effective for the protection area of 1H to 3H, but the 40% porosity proved to be effective for the protection area of 4H to 6H.

방풍팬스의 설치에 의한 저층건물 주변의 풍압특성을 분석하기 위하여 풍압실험을 실시하였다. 방풍팬스의 다공율은 0%와 20%을 중심으로 하였다. 방풍팬스와 저층건물의 거리는 1H-9H까지 범위안에서 측정을 하였다. 사용된 풍속은 6m/s로 일정하게 하였다. 저층건물의 측압공 위치는 정면과 측면 후면을 중심으로 총 54개를 측정하였다. 분석결과 다공률 20%일때는 측정거리 1H-3H일 때 다공률 40%일 때는 측정거리 4H-6H일 때 가장 효과적이었다.