Instantaneous Voltage Sag Corrector Using Series Compensator in Transfer Power Line Generator

송전선 직렬보상을 이용한 순시전압강하 보상기

  • Published : 2006.03.01

Abstract

This paper describes the novel control techniques design of VSC(Voltage Sag Corrector) for the purpose of power line quality enhancement. A fast detecting technique of voltage sag is implemented through the detection of instantaneous value on synchronous rotating do-reference frame. The first order digital filter is added in the detection algorithm to protect the insensitive characteristics against the noise. The relationship between the total detection time and cut-off frequency of the filter is described. The size of the capacitor bank used as the energy storage element is designed from the point of view of input/output energy with circuit analysis. Finally, the validity of the proposed scheme is proven through the simulated results.

Keywords

References

  1. Mark F. McGranaghan et al, 'Voltage Sags in Industrial Systems', IEEE Trans. on Industry Applications, Vol.29, No.2, pp.397-403, March/April, 1993 https://doi.org/10.1109/28.216550
  2. Alexander Kara et aI, 'Power Supply Quality Improvement with a Dynamic Voltage Restorer(DVR)', IEEE APEC, Vol. 2, pp.986-993, 1998
  3. R. Tounsi et al, 'Series Compensator for Voltage Dips : Control Strategy', EPE, pp.4929-4934, 1997
  4. G. Joos, 'Three-Phase Static Series Voltage Regulator Control Algorithms for Dynamic Sag Compensation', IEEE ISlE, pp.515-520, 1999
  5. R. S. Weissbach et al, 'Dynamic Voltage Compensation on Distribution Feeders using Flywheel Energy Storage', IEEE Trans. on Power Delivery, Vol.14, No.2, pp.465-471, April, 1999 https://doi.org/10.1109/61.754090
  6. M. F. Granaghan, 'Dynamic Sag Corrector : Cost Effective Industrial Power Line Conditioning', IEEE lAS, pp.1339-1344, 1999
  7. G. Andria et al, 'Inverter Drive Signal 'Processing via DFT and EKF', lEE Proc., Vol.137, pt. B, March, 1990