A Compensator for Lateral Current Reduction Applied to Autonomously Controlled UPSs Connected in Parallel

  • Sato Kazuhide Kazuhide (Department of Electrical and Computer Engineering., Yokohama National University) ;
  • Kawamura Atsuo (Department of Electrical and Computer Engineering., Yokohama National University)
  • Published : 2005.10.01

Abstract

This paper presents a compensator for reduction of the reactive lateral current in multiple autonomously controlled uninterruptible power supplies (UPS) connected in parallel. This compensator acts directly on the control equation for voltage amplitude and it provides an improved current distribution especially in the case of parallel connection of UPSs with different output power ratings. Observations show that the original control equation for output voltage amplitude is efficient for voltage regulation but it causes great variation of voltage levels. A compensator with the same structure is added to counterbalance the variation caused by the original control equation. Simulations show promising results with the employment of the proposed compensator. Our simulations are confirmed by experimental results using three UPSs with different output ratings and voltage limiters ($1\%$) connected in parallel under various conditions.

Keywords

References

  1. M. C. Chandorkar, D. M. Divan, and B. Banerjee, 'Control of distributed ups systems', in Proc. IEEE PESC'94, pp. 197-204, 1994
  2. E. A. A. Coelho, P. C. Cortizo; and P. F. D. Garcia, 'Small-signal stability for parallel-connected inverters in stand-alone ac supply systems', IEEE Trans. Ind. Applicat., Vol. 38, No.2, pp. 533-542, Mar./Apr. 2002 https://doi.org/10.1109/28.993176
  3. A. Kawamura and R. Watanabe, 'Autonomously decentralized control of multiple UPS' for higher reliability', in Proc. International Conference on Power EIectronics, pp. 836-840, 1998
  4. A. Kawamura and R. Fujii, 'Experiments for independent control of UPS based on complex systems', in Proc. 2002 lEE Japan Industry Applications Society Conference, No. 250, pp. 1311-1314 (in Japanese)
  5. E. K. Sato, A. Kawamura and R. Fujii, 'Theoretical and experimental verification of independent control for parallel-connected multi UPS's', in Proc. IEICE/IEEE INTELEC'03 , pp. 485-492, Yokohama, Oct. 2003
  6. E. K. Sato and A. Kawamura, 'Improvement of current balance in parallel connection of distinct output rating autonomously controlled UPS', in Proc. 2004 National Convention Record lEE Japan, No. 4-007, pp. 9-10, Mar. 2004
  7. E. K. Sato and A. Kawamura, 'Lateral current reduction by impedance drop compensator for multiple UPS's connected in parallel', in Proc. 2004 lEE Japan Industry Applications Society Conference, No. 1-119, pp. 531-534, Sep. 2004