An Improved Two-Terminal Numerical Algorithm of Fault Location Estimation and Arcing Fault Detection for Adaptive AutoReclosure

고속 적응자동재폐로를 위한 사고거리추정 및 사고판별에 관한 개선된 양단자 수치해석 알고리즘

  • Published : 2005.11.01

Abstract

This paper presents a new two-terminal numerical algorithm for fault location estimation and for faults recognition using the synchronized phaser in time-domain. The proposed algorithm is also based on the synchronized voltage and current phasor measured from the assumed PMUs(Phasor Measurement Units) installed at both ends of the transmission lines. Also the arc voltage wave shape is modeled numerically on the basis of a great number of arc voltage records obtained by transient recorder. From the calculated arc voltage amplitude it can make a decision whether the fault is permanent or transient. In this paper the algorithm is given and estimated using DFT(discrete Fourier Transform) and the LES(Least Error Squares Method). The algorithm uses a very short data window and enables fast fault detection and classification for real-time transmission line protection. To test the validity of the proposed algorithm, the Electro-Magnetic Transient Program(EMTP/ATP) is used.

Keywords

References

  1. Ge. Y, Sui. F, Xiao. Y, 'Prediction methods for preventing single-phase reclosing on permanent fault', IEEE Trans. on Power Delivery, Vol. 4, No. 1. pp. 114-121, 1989 https://doi.org/10.1109/61.19197
  2. M. B. Djuric, V.V. Terzija, ' A New Approach to the Arcing Faults Detection for Autoreclosure in Transmission Systems', IEEE Trans. on Power Delivery, Vol. 10, No. 4, pp. 1793-1798, 1995 https://doi.org/10.1109/61.473378
  3. Ruben D. Garzon, 'High Voltage Circuit Breakers', Marcel Dekker Inc., pp. 2-18, 1997
  4. A.T. Johns, R.K. Aggarwal, Y.H. Song, 'Improved Techniques for Modeling Fault Arcs on Faulted EHV Transmission Systems', IEE Proc. Gener. Transm. Distrib., Vol. 141, No. 2, pp. 148-154, March 1994 https://doi.org/10.1049/ip-gtd:19949869
  5. A.P. Strom, 'Long 60-Cycle Arcs in Air', AIEE Trans. Vol. 65, pp. 113-117, 1946
  6. B. Hofmann-Wellenhof, et al., 'Global Positioning System : Theory and Practice', Springer-Verlag, New York, 1992
  7. David Wells, 'Guide to GPS Positioning'. Ganadian GPS Associates, 1986
  8. 신중린, 조기선, 'GPS와 전력시스템', 제51권, 제3호, pp. 20-30, 2002
  9. Ying-Hong Lin, Chih-Wen Liu, Ching-Shan Chen, 'A New PMU-Based Fault Dectection/Location Techique for Tranmission Line with Consideration of Arcing Fault Discrimination-Part I :Theory and Algorithms', IEEE Trans. on Power Delivery, Vol. 19, No. 4, pp. 1587-1593, Oct. 2004 https://doi.org/10.1109/TPWRD.2004.832407
  10. IEEE Standard for Synchrophasors for Power Systems, IEEE Standard 1344-1995, 1344-1995 (R2001), December 1995
  11. Ying-Hong Lin, Chih-Wen Liu, Ching-Shan Chen, 'A New PMU-Based Fault Dectection/Location Techique for Tranmission Line with Consideration of Arcing Fault Discrimination-Part II:Performance Evaluation', IEEE Trans. on Power Delivery, Vol. 19, No. 4, pp.1594-1601, Oct. 2004 https://doi.org/10.1109/TPWRD.2004.835276
  12. M.B. Djuric, Z.M. Radojeic, V.V. Terzija, 'Numerical Algorithm for Arcing Faults Detection and Fault Distance Calculation on overhead line', Electric Machines and Power System, pp. 939-953. 1977
  13. M. B. Djuric, Z.M. Radojevic, V.V. Terzija, 'Arcing Faults Detection on Transmission Lines using Least square Technique', ETEP, Vol. 8, No. 6, pp. 437-443, Nov/Dec 1998 https://doi.org/10.1002/etep.4450080605
  14. Zoran Radojevic, Joong-Rin Shin, 'A New one-Terminal Numerical Algorithm for Adaptive Autoreclosure and Fault Distance Calculation', Tran KlEE, Vol.53A, No. 8, Aug. 2004, pp438-445
  15. A. Maikapar, 'Extinction of an Open Electric Arc', Elektrichestvo, Vol. 4, pp. 64-69, 1960
  16. Z.M. Radojevic, C.J. Lee, J.R. Shin, J.B. Park, 'Numerical Algorithm for Fault Distance Calculation and Blocking Unsuccessful Reclosing onto Permanent Faults', IEEE PES Gen., June 2005.Monte Carlo Approach for Power Estimation,' IEEE Trans. on VLSI systems, vol. 1, No. 1, pp.63-71, March 1993 https://doi.org/10.1109/92.219908