Direct and Indirect Membrane Integrity Tests for Monitoring Microbial Removal by Microfiltration

정밀여과(MF)막 미생물 제거율 모니터링을 위한 막 완전성시험

  • 홍승관 (고려대학교 공과대학 사회환경시스템공학과) ;
  • ;
  • Received : 2004.10.15
  • Accepted : 2004.12.06
  • Published : 2004.12.15

Abstract

The pilot study was conducted to (i) investigate the ability of various membrane integrity monitoring methods to detect changes in membrane integrity during operation, and (ii) determine the impact of membrane damage on microbial removal by microfiltration. Two variations of air pressure hold tests were investigated for direct integrity monitoring: pressure decay (PD) and diffusive air flow (DAF) tests which are most commonly used integrity tests for microfiltration (MF) membranes. Both PD and DAF tests were sensitive enough to detect one damaged fiber out of 66,000 under field operaing conditions. Indirect integrity monitoring such as turbidity and particle counting, however, responded poorly to defects in membrane systems. Microbial challenge study was performed using both new and deliberately damaged membranes, as well as varying the state of fouling of the membrane. This study demonstrated that MF membrane with nominal pore size $0.2{\mu}m$ was capable of removing various pathogens including coliform, spore, and cryptosporidium, at the level required by drinking water regulations, even when high operating pressures were applied. A sharp decrease in average log reduction value (LRV) was observed when one fiber was damaged, emphasizing the importance of membrane integrity in control of microbial contamination.

Keywords

References

  1. Adham, S.S., Jacangelo, J. G., Laine, J.M, (1995). Assessing Integrity. J. AWWA, 86(3) pp. 62-75
  2. Adham, S.S., Jacangelo, J.G., Laine, J.-M,(1996). Mechanism of Cryptosporidium, Giardia, and MS2 Virus Removal by MF and UF. J AWWA, 87(9) pp. 107-121
  3. Jacangelo, J.G., et al., (1991). Low-Pressure Membrane Filtration for Removing Giarda and Microbial Indicators. J. AWWA, 83(9) pp. 97-103
  4. Lozier, J. C., Jones, G., Bellamy, W., (1997). Integrated Membrane Treatment in Alaska. J. AWWA, 89(10) pp. 50-64
  5. McGahey, C., Olivieri, V.P., (1993). Mechanisms of Viral Capture by Microfiltration. Water Science Technology, 27: 3-4 pp. 307-310
  6. S. Hong, F. Miller, J. Taylor, (2001). 'Assessing Pathogen Removal Efficiency of Microfiltration by Monitoring Membrane Integrity', Water Science and Technology: Water Supply, 1(4) pp. 43-48
  7. USEPA (2003). Membrane Filtration Guidance Manual, pp. 4.1-4.3
  8. Yoo, R.S., Brown, D.R., Pardini, R.J., Bentson G.D., (1995). Microfiltration: A Case Study. J. AWWA, 87(3) pp. 38-49