Analysis of the Irradiated Solar Heat Effect on Indoor Thermal Environment of the ToP Floor Units of Apartment Houses in the Summer - On Condition that All Openings of the Units are Closed -

공동주택의 하절기 개구부 밀폐 시 지붕면 일사수열이 최상층 실내온열환경에 미치는 영향 분석

  • Choi, Dong-Ho (Dept. of Architecture, Catholic University of Daegu)
  • 최동호 (대구가톨릭대학교 건축학과)
  • Published : 2004.12.30

Abstract

In the summer, the irradiated solar heat gain through the roof has an effect on the thermal environment of the top floor units of apartment houses. This paper investigated the differences of the indoor air temperature and thermal comfort index between the top floor unit and the middle floor unit by measuring them at the sample houses. The purpose of this paper is to provide quantitative data about the irradiated solar heat gain during the summertime through the roof of an apartment house and these data to be the source to reevaluate the appropriate roof insulation efficiency. From this study, we obtained the brief results as follows. Indoor air temperature at the top floor unit is $1.2\sim2.2^{\circ}C$ higher than that of middle floor unit. The evaluation of the indoor thermal comfort index at each sample rooms reveals notable thermal differences between the two units. Top floor units need more cooling load during the summertime compared to middle floor units. Therefore, solutions to reduce solar Heat gain at top floor units to be considered.

Keywords

References

  1. http://www.moleg.go.kr/, "건축물의 설비기준 등에 관한 규칙 제21조", 법제처
  2. ダウ化工株式會社, "熱と環璄", 1988.06
  3. P. O. Fanger, 'Thermal comfort', Danish Technical Press., 1973