Experimental Study on Performance Evaluation of System Air-Conditioner using Compressor of PWM or Inverter Method (Cooling and Heating Characteristics)

PWM 방식과 인버터 방식의 압축기를 사용한 시스템 에어컨의 성능평가에 대한 실험적 연구(냉난방 특성)

  • 전용호 (선문대학교 기계공학과) ;
  • 김대훈 (선문대학교 기계공학과) ;
  • 허삼행 (선문대학교 기계공학과) ;
  • 권영철 (선문대학교 기계공학과) ;
  • 문제명 (삼성전자 시스템가전사업부) ;
  • 홍주태 (삼성전자 시스템가전사업부)
  • Published : 2003.09.01

Abstract

In the present study, the heating and cooling characteristics of system air-conditioner using a PWM compressor or a BLDC inverter compressor are investigated by the psychometric calorimeter using air enthalpy method. Cooling and heating capacities, power inputs and COPs are measured at the low, moderate, high loads under the cooling and heating standard conditions. At cooling conditions, the capacity of the PWM system is larger than that of the inverter case. Due to large power input, however, low COPs are measured under total load ranges. At heating conditions, the capacity of the PWM method is a little larger than that of the inverter case, except high load range. Since power input is low, large COPs are measured at moderate and high load ranges, which are different from cooling data. This shows that the PW system compared with the inverter case has good energy consumption efficiency at moderate and high load ranges except low load range. And when the system A/C is operated under the cooling and heating standard conditions, COPs are nearly uniform at total load ranges.

Keywords

References

  1. Proceeding of SAREK The experimental study on the comparison in performance of the system which used modulated compressors Kim,C.M.;Hwang,Y.J.;Ryu,Y.H.;Cho,K.S.
  2. Proceeding of SAREK v.14 no.2 Benchmark performance analysis of vapor compression system with capacity modulation compressor Ryu,Y.H.;Hwang,Y.J.Kim,C.M.;Cho,K.S.
  3. Final Report, RRC. Experimental study on the efficiency improvement of DVS system air-conditioner using the digital scroll compressor Kwon,Y.C.;Lee,Y.S.;Kim,D.H.;Jun,Y.H.
  4. Korean Journal of Air-Conditioning and Refrigeration Engineering v.15 no.6 Experimental study on the cooling and heating characteristics of system A/C applying the digital scroll compressor Kwon,Y.C,;Kim,D.H.;Jun,Y.H.;Lee,Y.S.;Chang,K.S.;Moon,J.M.;Youn,B.;Hong,J.T.
  5. Korean Journal of Air-Conditioning and Refrigeration Engineering v.15 no.7 Experimental study on performance evaluation of system A/C using PWM or Inverter method(heating characteristics at low temperature conditions) Kwon,Y.C.;Kim,D.H.;Jun,Y.H.;Lee,Y.S,;Moon,J.M.;Hong,J.T.
  6. KS C 9306 Air conditioners, Korean agency for technology and standards
  7. Final Report Sunmoon university air-enthalpy calorimeter performance evaluation project KTL
  8. ASHRAE Standard ANSI/ASHRAE 116-1983 Method of testing for seasonal efficiency of unitary air conditioners and heat pumps ASHRAE
  9. Proceedings of the SAREK Rotary compressor using a brushless DC motor Soh,S.G.;Kim,S.K.;Lee,S.K.;Park,Y.S.
  10. Proceedings of the SAREK An experimental study on the heating capacity improvement at low temperature condition of system air-conditioner using the digital scroll compressor Hong,J.T.;Jang,G.S.;Kim,D.Y.;Kim,J.Y.;Moon,J.M.;Youn,B.;Shim,S.C.