DOI QR코드

DOI QR Code

신흡수용액을 이용한 중온수 흡수식 냉동기의 사이클 해석

Cycle Analysis of Hot Water Driven Absorption Refrigerator with New Working Absorption Solution

  • 발행 : 2002.09.01

초록

Performance extension of the absorption refrigerator with LiBr solution is often faced to operate very close to the crystallization limit. Especially in the development of an air-cooled cycle, the crystallization of working solution in the system is a very difficult problem to overcome. This paper describes the cycle of hot water driven absorption system using a new working absorption solution instead of LiBr solution to improve the efficiency. In this study, we found out the characteristics of new working absorption solution through the cycle simulation and compared LiBr solution to evaluate. The effect of cooling water temperature, weak solution flow rate, hot water temperature and hot water flow rate were also examined. The COP is increased 22% higher in the case of LiBr+Li1+LiC1+LiNO$_3$$H_2O$, 2% LiBr+HO(CH$_2$)$_3$OH+$H_2O$ than that of LiBr solution for the same operation condition.

키워드

참고문헌

  1. Seol, W. S., Kwon, O. K., Moon, C. G. and Yoon, J. I., 2000, 'Heat Transfer Enhancement with Surfactants in Horizontal Bundle Tubes on Absorber,' Transactions of the KSME B, Vol. 24, No. 8, p. 1097, 1103
  2. Yoon, J. I., Kwon, O. K. and Moon, C. G., 1999, 'Influence of Surfactant on Heat Transfer of Air-Cooled Vertical Absorber,' Korean Journal of Air-Conditioning and Refrigeration Engineering, Vol. 11, No. 6, pp. 740-748
  3. Seol, W. S., Kwon, O. K. and Yoon, J. I., 1998, 'Experimental Investigation of Enhanced Heat and Mass Transfer for $LiBr/H_2$O Absorber,' Korean Journal of Air-Conditioning and Refrigeration Engineering, Vol. 10, No. 5, pp. 581-588
  4. Kwon, O. K. and Yoon, J. I., 1999, 'Heat and Mass Trsnfer of Helical Absorber on Household Absorption Chiller/Heater,' Korean Journal of Air-Conditioning and Refrigeration Engineering, Vol. 11, No. 5, pp. 570-578
  5. MeNeely, L. A., 1979, 'Thermodynamic Properties of Aqueous Solution of Lithium Bromide,' ASHRAE Transactions, Vol. 85, Pt. 1, pp. 413-434
  6. Nishiyama, N., Fujikura, K., Wakimizq, H., Kaneko, T., Yamazaki, S. and Izu, M., 1994, 'R&D of Absorption Heat Pump System Using Mew Working Fluid to Utilize Treated Sewage Water,' Trans. of the JAR, Vol. 11, No. 2, pp. 219-230
  7. Park Y., Kim J.S. and Lee H., 1997, 'Physical Properties of the Lithium Bromide+1,3 Propanediol+Water System,' Int J. Refrig., Vol. 20, No. 5, pp. 319-325 https://doi.org/10.1016/S0140-7007(97)00021-2
  8. Kwon, O. K. and Yoon, J. I., 1999, 'Cycle Analysis of Air-Cooled Double-Effect Absorption Cooling System Using $H_2O/LiBr+HO(CH_2)_3OH$,' Transactions of the KSME B, Vol. 23, No. 2, pp. 272-280
  9. Kwon, O. K., Lim, J. K. and Yoon, J. I., 2000, 'Characteristic of Heat and Mass Transfer on Helical Absorber Using New Working Fluid,' Proceedings of the KSME 2000 Spring Annual Meeting B, pp. 228-233
  10. Seol, W. S., Kwon, O. K., Moon, C. G. and Yoon, J. I., 1998, 'An Investigation on the System Characteristics of Hot Water Driven Absorption Chillers with New Absorption Solution,' Proceedings of the KSME 1998 Fall Annual Meeting B, pp. 160-165
  11. Homma R., Nishiyama N. and Wakimizu H., 1993, 'International Absorption Heat Pump Conference ASME,' International Absorption Heat Pump Conference ASME, pp. 273-278