A study on the Application of a Monitoring System for Gas Insulaterd Switchgear

가스절연개폐장치용 감시시스템 적용에 관한 연구

  • 김정배 ((주)효성 중공업연구소) ;
  • 김민수 ((주)효성 중공업연구소) ;
  • 송원표 ((주)효성 중공업연구소) ;
  • 김덕수 ((주)효성 중공업PG 임원) ;
  • 전찬석 (철도청 건설본부 전기설계과) ;
  • 길경석 (한국해양대 공대 전기공학과)
  • Published : 2002.01.01

Abstract

ln this paper, it was reported the developed results of the monitoring unit for 72.5kY GIS which it is one part of the monitoring system for the substation that Korea Railway Company is promoting. In order to monitor the operational status of GIS, four parameters were chosen: the number of times of the circuit breaker switching, tightness of the gas-sealed units (circuit breaker / disconnecting switch / earthing switch), the number of times of the lightning arrestor operating and the leakage current of the lighting arrester. We constructed the monitoring system that can be judged the operating condition of the GIS from the signal of the suitable sensor for the purpose. Therefore, it is possible to on line monitoring for the condition of the GlS without efforts of the Periodic inspection.

Keywords

References

  1. 김정배 외, '초고압 가스절연개폐장치의 스마트 진단 시스템 개발', 전기산업신기술세미나논문집. pp.l69 pp.l77, 2000년 11월
  2. T. Sakakibara, H. maehara, S. Maruyama, A. kobayashi, S. Kuninori, 'Heliability verification of system applying a microprocessor in a high voltage gas insulated substation', IEEE Trans. on Power Delivery, Vol. l3, No.4, 1105-1113, 1998 https://doi.org/10.1109/61.714468
  3. Endre Mikes, 'State of the art high voltage switchgear; Availability, reliability, Functionality and condition based maintenance aspects of circuit breakers with spring mechanism', CLDEM, I996
  4. V. Rees, M. Burgard, G. Krutmann, B. Feuchter, 'Advanced digital control and monitoring of gas insulated switchgear (GIS)', CIGRE 2000, session paper 23/39 08
  5. Catalogue of WIKA Gas Density Measurement, PM 02.31 - PE85.04, 2000
  6. Asle Schel, 'Diagnostic techniques for surge arresters with main reference to on-line measurement of resistive leakage current of matal-oxide arresters', CIGRE 2000, session paper P1-05