초록

In order to develop the compact and flexible heat exchangers, we made the helically coiled heat exchangers. They can be manufactured with small diameter copper tubes without the need for fins; inner diameter=1.0 mm, straight tube length=1.5 m. The experiments were carried out with the following conditions; evaporation pressure=0.6 MPa, air velocity=0.7 ∼ 1.7 m/s, and working fluid=R-22. Pressure drop and heat transfer coefficient of heat exchangers were experimented according to the air velocity. The results of heat transfer coefficient show a 35% beneficial increase fur these heat exchangers over the other covered fin-tube heat exchangers. A cooling capacity of about 3 kW was obtained with an air velocity of 1.5 m/s. The distribution header has also been designed fur efficient distribution of refrigerant flow.

키워드

참고문헌

  1. 金鐘秀, 勝田正文, 1995, 'CFC 대체냉매용 고성능 열교환기의 개발,' 냉동.공조공학, Vol. 14, No. 5, pp. 9-19
  2. 吳田昌俊, 小林利行, 三島嘉一郞, 西原英, 1997, '小口徑円管內强制流動液單相流およぴ沸勝相流の壓力損失と熱傳達,' 日本機械學會論文集 B編, 63卷, 615?, pp.216-224
  3. Wilmarth, T. and Ishii, M., 1994, 'Two-Phase Flow Regimes in Narrow Rectangular Vertical and Horizontal Channels,' Int. J. Heat Mass Transfer, Vol. 37, No. 12, pp. 1749- 1758 https://doi.org/10.1016/0017-9310(94)90064-7
  4. 江崎秀司, 深野徹, 1995, '水な多分管岐への偏流に關する硏究,' 日本機械學會論文集(B編), 61卷, 589?, pp. 3130-3136
  5. 渡?學, 1998, '高性能空調機のための細管多連分岐蒸發器のおける氣液:相流の流分配機構に關する硏究,' 早稻田大學博士學位論文
  6. Taylor G. I., 1929, 'The Criterion for Turbulence in Curved Pipes,' Proc. Roy. Soc. London. A 124, pp. 234 -- 249
  7. Dean W. R., 1927, 'Note on the Motion of Fluid in a Curved Pipe,' Phil. Mag., Vol. 4, pp. 208-223
  8. Kazi, M., Mori, K., Oishi, M., Nakanishi, S. and Sawai, T., 1997, 'Boiling Heat Transfer and Dryout Characteristics in Helically Coiled Tubes,' Experimental Heat Transfer, Fluid Mechanics and Thermodynamics 1997, pp. 649-656
  9. Feng, Z. P., Guo, L. J., and Chen, X. J., 1997, 'Forced Convection Boiling Heat Transfer in Helically Coiled Tubes with Various Helix Axial Angles,' Experimental Heat Transfer, Fluid Mechanics and Thermodynamics 1997, pp. 593-599
  10. 김주원, 김정훈, 서석기, 김정훈, 김종수, 2000, '극세관 헬리컬 코일 증발관내 R-22의 열전달 및 압력손실 특성,' 대한기계학회논문집(B), 제24권 제5호, pp.699-708
  11. Kline, S. J. and McClinetock, F., 1953, 'Describing Uncertainty in Single Sample Experiments,' Mechanical Engineering, Vol. 75, pp.3-8
  12. 윤점열, 이욱용, 이관수, 1996, '핀-관 열교환기에 사용되는 핀의 종류와 연구동향,' 공기조화냉동공학회지, Vol. 25, No. 2, pp. 137-150