The objective of the present study is to investigate the performance of electronic scale mitigation unit(ESMU), which reduces the amount of scale in a heat exchanger. The circular tube with diameter of 19mm and plate-and-frame heat exchangers with 20 thermal plates were used for the tests. In order to accelerate the rate of scale in a laboratory test, artificial hard water of 1000ppm(as CaCO$_3$) was recirculated at a flow rate of 5 lpm, 7 lpm, and 9 lpm throughout the tests. The effect of ESMU on the scale thickness and overall heat transfer coefficients was examined. The test results showed that the ESMU could reduce the scale deposits even in the acceleated test.

Keywords

References

  1. Taborek, J., Aoki T., Ritter R. B., Palen J. W. and Knudsen J. G., 1972, Fouling: 'The major Unresolved Problem in Heat Transfer,' Chemical Engineering Progress, Vol. 68, No. 2, pp. 59-67
  2. Suitor, J. W.,Marner, W. J. and Ritter, R. B., 1977, 'The History and Status of Research in Fouling of Heat Exchangers in Cooling Water Service', The Canadian J. of Chem. Eng., Vol. 55, pp. 374-380
  3. Parker, D., 1985, 'An Investigation of the Role of the Magnetic Water Treatment Devices in Calcium Carbonate Scale Formation, M. S. Thesis, Baylor University, Waco, TX
  4. Maggard, S., 1989, 'A Chemometric Analysis of a Magnetic Water Treatment Device, Ph. D. Dissertation, Baylor University, Waco. TX.
  5. Fan, C. F., 1997, 'A Study of Electronic Descaling Technology to Control Precipitation Fouling, Ph. D. Thesis, Drexel University, Philadelphia, PA.
  6. Cho, Y. I., Choi, B. G., and Drazner, B. J., 1998, 'Electronic Anti-Fouling Technology to Mitigate Precipitation Fouling in Plate-and-frame Heat Exchangers,' Int. J. Heat Mass Transfer, Vol. 41, N o. 17, pp. 2565-2571 https://doi.org/10.1016/S0017-9310(97)00347-5
  7. Cho, Y. I., and Choi, B. G., 1999, 'Validation of an Electronic Anti-Fouling Technology in a Single-Tube Heat Exchanger,' Int. J. Heat Mass Transfer, Vol 41, pp. 1491-1499 https://doi.org/10.1016/S0017-9310(98)00196-3
  8. 서해성, 모경우, 김동현, 모정하, 1999, '열교환기의 효율향상을 위한 전자식 스케링완화장치,' 대한기계학회 호남지부 학술대회 논문집, pp. 117-121
  9. 서해성, 김경우, 이상설, 이건휘, 모정하, 김동현, 1999, '열교환기용 전자식 스케일완화장치의 성능평가,' 대한기계학회 추계학술대회 논문집 B, pp. 409-412
  10. 서해성, 신상철, 김경우, 모장하, 김동현, 2000, '판형 열교환기에 대한 전자식 스케일완화장치의 성능평가,' 대한기계학회 춘계학술대회 논문집B, pp. 13-17
  11. Choi, B. G., 1998, 'A Study of Fouling Control in Heat Exchangers with Electronic Anti-Fouling Technology, Ph.D. Thesis, Drexel University, Philadelphia, PA.