• Title/Summary/Keyword: Electronic Scale Mitigation Unit

Search Result 2, Processing Time 0.016 seconds

Performance Evaluation of Scale Mitigation Unit for Heat Exchangers (열교환기에 대한 스케일 완화장치의 성능평가)

  • Mo, Jeong-Ha;Sin, Sang-Cheol;Kim, Gyeong-U
    • Transactions of the Korean Society of Mechanical Engineers B
    • /
    • v.25 no.9
    • /
    • pp.1149-1156
    • /
    • 2001
  • The objective of the present study is to investigate the performance of electronic scale mitigation unit(ESMU), which reduces the amount of scale in a heat exchanger. The circular tube with diameter of 19mm and plate-and-frame heat exchangers with 20 thermal plates were used for the tests. In order to accelerate the rate of scale in a laboratory test, artificial hard water of 1000ppm(as CaCO$_3$) was recirculated at a flow rate of 5 lpm, 7 lpm, and 9 lpm throughout the tests. The effect of ESMU on the scale thickness and overall heat transfer coefficients was examined. The test results showed that the ESMU could reduce the scale deposits even in the acceleated test.

Performance Evaluation of Electronic Scale Mitigation Unit for Plate Heat Exchanger (판형 열교환기에 대한 전자식 스케일 완화 장치의 성능평가)

  • Seo, Hae-Sung;Shin, Sang-Chul;Kim, Kyong-Woo;Moh, Jeong-Hah;Kim, Dong-Hyun
    • Proceedings of the KSME Conference
    • /
    • 2000.04b
    • /
    • pp.13-18
    • /
    • 2000
  • The objective of the Present study is to investigate the performance of electronic scale mitigation unit(ESMU), which reduces the amount of scale in a heat exchanger. A plate heat exchanger with 20 thermal plates is used for the tests. In order to accelerate the rate of fouling in a laboratory test artificial hard water of 2000 ppm(as $CaCO_3$) is recirculated at a flow rate 5L/min throughout the tests. The overall heat trans(or coefficients and fouling factors are examined. Results show that the ESMU technology can significantly reduce the scale deposits.

  • PDF