Abstract
This paper is introducing a newly developed spark-gap switch with dual trigger system, into which the current from the voltage source is injected along with the test sequence during the synthetic testing of high voltage circuit-breaker. The currently-used spark gap switch is narrow in operating range due to the use of the method of triggering energy being injected by single way. As a result, the frequent happening of misoperation has greatly reduced the test quality and test efficiency and has required the cost of maintenance excessively. In this study, accordingly, in order to basically remove these problems, another triggering system is installed to the opposite direction on the existing triggering system; attaching the same time and the same rising time of pulse wave as on the existing system, so that at a comparatively trigger gap distance from the main electrode(the gap can be operated at 60% of self-break voltage, while at 80% in the current system), the main electrode has been enabled to be closed by the development of spark gap switch with dual trigger system.