Abstract
Based on the results in the first-part paper, PSS tuning methods including the determination of PSS gain and compensation of phasor lagging are investigated in this second part. In the phase compensation, PSS should compensate phase lagging, resulted from power system-generator-excitation system loop, to provide damping torque in equal phase with the generator speed. Also, PSS gain should be determined to provide maximum damping torque as much as possible without the other modes unstable. In this paper, gain tuning method using the root-locus and the phase compensation of PSS at the one machine with infinite bus system are presented. The differences between PSS tuning at the tuning condition and at the least-stable condition are also discussed.