Characteristics of Thermal Environments and Evaluation of Thermal Comfort in Office Building in Winter

겨울철 사무실내 온열환경 특성 및 쾌적성 평가

  • 배귀남 (한국과학기술연구원 기전연구부) ;
  • 이철희 (한국과학기술연구원 기전연구부) ;
  • 이춘식 (한국과학기술연구원 기전연구부) ;
  • 최항철 (한국과학기술연구원 기전연구부)
  • Published : 1995.05.01

Abstract

In this study, indoor thermal parameters were measured to investigate the characteristics of thermal environments and 138 occupants were questioned to evaluate Korean thermal comfort in office building in winter. Thermal sensation was estimated by using PMV(Predicted Mean Vote) and ET*(New Effective Temperature) indices. Comparing present experimental result with international standards and that of other research, Korean thermal responses were discussed. Seasonal difference between summer and winter was also discussed. It was found that TSV(Thermal Sensation Vote) is more sensitive than PMV to the variation of temperature and that the measured percentage of dissatisfied is higher than PPD(Predicted Percentage of Dissatisfied) in real office building environments. By regression analysis, the following regression equation has been obtained; TSV=0.432ET*-8.814 and neutral temperature is $20.4^{\circ}C$ in this case. Thermal comfort range based on 80% satisfaction is also $19.4{\sim}22.4^{\circ}C$.

Keywords

Acknowledgement

Supported by : 과학기술처