An Experimental Study on the Pressure Drop and Heat Transfer Performance in Tubes with Three Dimensional Roughness

삼차원 조도관의 압력손실 및 열전달 성능에 대한 실험적 연구

  • Published : 1995.05.01

Abstract

In this study, pressure drop and heat transfer coefficients were measured in tubes with three dimensional roughness. Dimples were made by rotating the saw-tooth shaped finning disc on the outer tube surface. Resultant dimple shape was oval. Friction and heat transfer tests were performed with a range of roughness variables-roughness height 'e', axial roughness pitch 'p', circumferential roughness pitch 'z'. Within the test range, tube with e=0.5mm, z=5mm, p=3mm performed best. The efficiency ratio(rati of the heat transfer improvement and the pressure drop increase) of the tube approached 1.0 at low Reynolds number, and it was higher than that of the two-dimensional roughess tube of the same roughness height. Test data were predicted by 'discrete element method'. Results show that discrete element method underpredicts the friction data by 2% to 32%, and overpredicts the heat transfer data by-12% to 113%.

Keywords

Acknowledgement

Supported by : 학술진흥재단