Control of Refrigerating Compressor Capacity Using Inverter

인버터를 이용한 냉동용 압축기의 용량 제어

  • Published : 1993.05.01

Abstract

Recently, efforts of decreasing energy consumption are continously increased and user's preference is also diversified in refrigeration and air conditioning systems. Thus, in order to satisfy these demands, high efficiency, high intelligence, and energy saving for those systems are essential. As the basic study for diverse functions and intelligence of those systems, we investigated the response characteristics through the compressor capacity control concerned with superheat and refrigeration room temperature. And, response characteristics are investigated experimentally by using micro computer based PWM inverter control method. Experimental result of the conventional on-off control method is given in order to be compared to the results of inverter control method. The results obtained through this study are summarized as follows. It is shown from the experimental results of the on-off control method that the range of temperature variation around the steady state ($-18^{\circ}C$) is very large (about $7{\sim}8^{\circ}C$) and the settling time bringing the steady state is not found. In the inverter control method, we can see that the refrigeration room temperature after reaching the setting temperature is very stable without fluctuation and a robust control for disturbance such as opening the door has been realized.