공기식 집열창 시스템이 설치된 건물의 동적부하 해석

Time Dependent Thermal Load Analysis of the Building with an Airflow Window System

  • 발행 : 1992.05.01

초록

It has been known that the application of an airflow window system reduces the energy consumption compared with conventional double pane window in a building. But how to analyze thermal load in a building with an airflow window system has not been well known. so two kinds of method (Mode 1 and Mode 2) to analyze time dependent thermal load of the building with an airflow window system are presented in this study. The results of load analysis about the model building(total area : $4521m^2$, 3 floors) by Mode 2 show that the maximum cooling and heating load in a building with an airflow window system are decreased about 12-17% and about 19.5% than with double pane glass window, and yearly energy consumption with an airflow window system is saved about about 20% than with double pane glass window.

키워드