The bearing capacity of the wall against the eccentric load when the washbasin was attached on the ALC block wall was tested. Test methods are BS EN 14688 and BS 5234-2. Tests in accordance with BS EN 14688 showed that the holding capacity of steel was much stronger and more stable when HA-II (chemical anchor) was used than when the washbasin was fixed using HA-I (plastic anchor). As an experimental result according to the Annex K of BS 5234-2, the bearing capacity of ALC block wall corresponded to the "stage in which the force works(performance grade) 1,500N" for all of the cases where a washbasin is fixed using two types of the wall's dedicated anchors(HA-I and HA-II).