Acceptable Supply Air Conditions of Dedicated Outdoor Air System for a High-rise Apartment Building

초고층 공동주택 외기전담 시스템 기반 중앙 공급식 환기시스템의 적정 급기조건 설정

  • Kim, Min-Hwi (Dept. of Architectural Engineering, Sejong University) ;
  • Kim, Jin-Hyo (Dept. of Architectural Engineering, Sejong University) ;
  • Kwon, Oh-Hyun (Dept. of Architectural Engineering, Sejong University) ;
  • Jeong, Jae-Weon (Dept. of Architectural Engineering, Sejong University)
  • Received : 2009.11.03
  • Accepted : 2009.11.10
  • Published : 2009.11.19

Abstract

The main thrust of this paper is to investigate acceptable supply air conditions of a dedicated outdoor air system (DOAS) for highrise apartment buildings. As for a typical $132-m^2$ apartment unit, it was assumed that centralized DOAS-Ceiling Radiant Cooling Panel was installed. Transient behavior and control characteristics of each system were modeled numerically using a commercial equation solver program. The optimized dew point temperature of the DOAS was discussed on the basis of the ASHRAE standard 62.1-2007 and the current Korean ventilation standard for apartments. It was found that the optimized dew point temperature of the DOAS supply air accommodating total latent load of a space is $11-12^{\circ}C$ and the appropriate supply air temperature of the DOAS is $11-12^{\circ}C$ in cooling period and neutral temperature of $18-20^{\circ}C$ in intermediate period.