Proceedings of the Korean Institute of Electrical and Electronic Material Engineers Conference (한국전기전자재료학회:학술대회논문집)
- 2006.11a
- /
- Pages.326-327
- /
- 2006
Reliability Evaluation of Polymer Arrester with Sealing Integrity for Station and Substation
발.변전용 폴리머 피뢰기의 기밀특성에 따른 신뢰성 평가
- Published : 2006.11.09
Abstract
The paper describes the development of arrester for 154kV class power station and substation. The arrester employs silicone insulating materials for Its housing, instead of the conventional porcelain housing. The sealing integrity is related to safe operation of surge arrester, the prime failure reason of porcelain housed arresters is moisture ingress. In this paper, the sealing integrity of polymeric surge arresters for ultra high voltage is investigated with moisture ingress test. The diagnostic techniques are discusses, including watt loss, partial discharge, AC leakage current, 1mA DC voltage and residual voltage.