Minimum Ventilation Rate of Kindergarten in the respect of IAQ

실내공기질을 고려한 유치원 보육실의 적정 환기량 검토

  • Published : 2006.06.21

Abstract

Indoor Air Quality Guideline of Kindergarten in korea didn't consider the vulnerable properties of children to indoor air pollutants. For this reason, Suggestion for the IAQ guideline of formaldehyde and minimum ventilation rate was made in this study. Suggested IAQ guidelines for formaldehyde in the respect of children's vulnerable immune system is $30{\mu}g/m^3$ and $50{\mu}g/m^3$, and for the ventilation rate 11.9 ACH, 5.8 ACH, respectively. This value is based only formaldehyde and CO2 concentrations in child-care room of Kindergarten and needed to be verified by further investigations and studies. However it is discovered that lower formaldehyde concentration can do mal-effects to children's health by literature review.