베어관을 이용한 30RT급 하이브리드 밀폐형 냉각탑의 성능특성에 관한 실험적 연구

An Experimental Study on Performance Characteristic of 30RT Closed-Type Hybrid Cooling Tower using Bare Tube

  • 전철호 (부경대학교 냉동공조공학과 대학원) ;
  • 이호생 (부경대학교 냉동공조공학과 대학원) ;
  • 문춘근 (부경대학교 냉동공조공학과 대학원) ;
  • 김재돌 (부경대학교 기계공학부) ;
  • 윤정인 (부경대학교 기계공학부)
  • 발행 : 2005.06.26

초록

In this study, the experiment of thermal performance about closed-type hybrid cooling tower was conducted. A closed type cooling tower is a device similar to a general cooling tower, but with cooling tower replaced by a heat exchanger. The test section for this experiment has the process that the cooling water flows from top part of heat exchanger to bottom side in the inner side of tube, and spray water flows gravitational direction in the outer side of it. Air contacts of tube outer side are counterflow. The heat transfer pipe used in this experiment is a bare type tube having an outside diameter of 15.88mm. In this experiment, heat performances of the cooling tower are calculated such as overall heat transfer coefficient of between the process fluid and air, cooing capacity and pressure drop.