• Title/Summary/Keyword: Closed type cooling tower

Search Result 4, Processing Time 0.018 seconds

An Experimental Study on Performance Characteristic of 30RT Closed-Type Hybrid Cooling Tower using Bare Tube (베어관을 이용한 30RT급 하이브리드 밀폐형 냉각탑의 성능특성에 관한 실험적 연구)

  • Jun, Chul-Ho;Lee, Ho-Saeng;Moon, Choon-Geun;Kim, Jae-Dol;Yoon, Jung-In
    • Proceedings of the Korean Society of Marine Engineers Conference
    • /
    • 2005.06a
    • /
    • pp.1096-1101
    • /
    • 2005
  • In this study, the experiment of thermal performance about closed-type hybrid cooling tower was conducted. A closed type cooling tower is a device similar to a general cooling tower, but with cooling tower replaced by a heat exchanger. The test section for this experiment has the process that the cooling water flows from top part of heat exchanger to bottom side in the inner side of tube, and spray water flows gravitational direction in the outer side of it. Air contacts of tube outer side are counterflow. The heat transfer pipe used in this experiment is a bare type tube having an outside diameter of 15.88mm. In this experiment, heat performances of the cooling tower are calculated such as overall heat transfer coefficient of between the process fluid and air, cooing capacity and pressure drop.

  • PDF

A Study on the Factors of affecting the Heat Exchanger for Closed Cooling Tower (밀폐형 냉각탑용 열교환기의 성능에 영향을 미치는 인자에 관한연구)

  • Lee, Sang-Sik;Yoo, Seong-Yeon;Kim, Jin-Hyuck;Ryu, Hae-Sung;Park, Hyoung-Joon
    • Proceedings of the SAREK Conference
    • /
    • 2008.11a
    • /
    • pp.250-255
    • /
    • 2008
  • Most high-rise building and large building require a cooling tower. Closed cooling tower is a low noise and the high efficiency. also Closed cooling tower is available for four season. Performance of Closed cooling tower is judged by heat transfer coefficient. In this study, Heat transfer coefficient is compared with air velocity, spray flow, heat exchanger type.

  • PDF

Thermal Performance Characteristics of Closed-Wet Cooling Tower (밀폐형 냉각탑의 열성능 특성에 관한 실험적 연구)

  • Sarker, M.M.A.;Kim, E.P.;Moon, C.G.;Yoon, J.I.
    • Journal of Power System Engineering
    • /
    • v.9 no.2
    • /
    • pp.88-92
    • /
    • 2005
  • The experiment of thermal performance about closed-wet cooling tower was conducted in this study. A closed cooling tower is a device similar to a general cooling tower, but with cooling tower replaced by a heat exchanger. The test section for this experiment has the process that the cooling water flows from the top of the heat exchanger to the bottom side in the inner part of the tube, and spray water flows in the gravitational direction in the outer side. Air comes in direct contact with the spray water at the outer side of the tube while passing from the lower the upper part having a counterflow to the spray water. The heat transfer pipe used in this experiment is a bare-type tube having an outer diameter of 15.88mm. The heat exchanger is consisted of seven rows and fifteen columns. In this experiment, thermal performance of the cooling tower is derived from overall heat transfer coefficients between the process fluid and sprayed water and volumetric overall mass transfer coefficient between sprayed water and air.

  • PDF

Characteristics of Closed Circuit Cooling Tower with Variation of Tube Diameter (멀티패스 밀폐식 냉각탑의 관경변화 특성)

  • Shim, Gyu-Jin;Lee, Ho-Saeng;Kim, Eun-Pil;Yoon, Jung-In;Kwon, O-Ick
    • Proceedings of the SAREK Conference
    • /
    • 2008.11a
    • /
    • pp.531-536
    • /
    • 2008
  • This paper presents experimental result of characteristics about Closed circuit Cooling Tower having a rated 2RT. The experimental apparatus has been set-up with a conventional type system. The test section is heat exchangers of cooling tower that consist of different vertical tubes, 15.88mm with 10 rows and columns and 19.05 mm with 8 rows and 12 columns. The main results were summarized as follows : The values of heat and mass transfer coefficients of cooling tower operating with two paths are higher than these with one path. Cooling capacity per unit volume using 15.88mm tubes are higher than 19.05mm tubes.

  • PDF