XLPE 내부 보이드 위치변화에 따른 부분방전 특성 및 수명예측

Life Time Diagnosis and Partial Discharge Characteristics due to shift of Void Position in XLPE

  • 발행 : 2005.07.07

초록

To estimate a electrical performance of the extra high voltage XLPE cable the discharge properties due to shift of void position were investigated. The $\Phi-q-n$ properties have been measured at room temperature by rising voltage ratio of 0.5[kV]. An obtained data was stored to personal computer through A/D converter. The period of applied wave form and discharge values were divided into 64 parts and discharge values generated during 10 seconds were accumulated by phases. As a result, it was confirmed that the charge, phase angle and counts of discharge changed due to void position.