A Study on unperfected circuiting current of undergrounded cable

지중송전케이블의 불완전 순환전류에 관한 연구

  • Published : 2004.05.21

Abstract

In this paper, we studied on permissible current of unperfected earthing for cross-bond system. The factors of unperfected earth were jacket damage, cross-bonding mistake, arrestor damage, effect of other circuit but we only studied permissible current of arrestor or jacket damage. In the result, we earned that permissible current of normal 154[[kV]] CV $1C{\times}400SQMM$ cable is 760[A] but current of unperfected earthing cable is 76[A], unperfected earthing confirmed that accident of underground cable could occur. So, we could confirmed that Earthing resistance of unperfected earthing need to limit.