A Study on The Reducing Harmonics of Static Var Compensator using PAM Inverter

PAM 인버터를 이용한 무효전력보상장치의 고조파 저감에 관한 연구

  • Published : 2002.07.08

Abstract

This paper presents SVC which use PAM method and eliminate harmonics. Inverter is connected directly so that SVC improve output voltage waveform into 24 steps. Inverter output waveform THD is reduced to 6.89%. Leading control of reactive power generated in power system is possible. Snubber is added to reduce switching loss.

Keywords