Reliability Assessment of Polymer Insulators by Accelerated Aging Test

가속열화시험에 의한 폴리머애자의 신뢰성 평가

  • 한채홍 (한국전력공사 전력연구원 배전기술그룹) ;
  • 이병성 (한국전력공사 전력연구원 배전기술그룹) ;
  • 정종욱 (한국전력공사 전력연구원 배전기술그룹)
  • Published : 2001.05.11

Abstract

In order to assess the long-tenn reliability of polymer insulators for distribution power systems, we have developed the accelerated aging test method which can simulate the operation conditions. In this study, 3000 hours aging test for 4 kinds of polymer insulators has been completed by the developed accelerated aging test. After 3000 hours aging test, visual inspection and electrical tests were carried for identifying a change of characteristics. Some specimens showed the surface erosion and the manufacturing defect. In the electrical tests, the wet flashover voltage was significant1y decreased by the accelerated aging test. In comparison with the field-aged polymer insulators, it can be concluded that the developed test method can evaluate the long-tenn reliability within short time and screen the manufacturing defect.

Keywords