Abstract

When the current of a power converter is controlled with a digital controller, it generally shows the error due to execution time delay. The error may be considerable in such systems as active power filters wherein the current varies steeply even in steady state, as well as in transients. Therefore, it is of particular importance to compensate the time delay effect in a digitally-controlled active power filter. This paper introduces a modification of so-called predictive current control, by taking the control time delay into consideration. The results of simulation and experiment with a 10 kVA active power filter prototype show considerable improvement in current tracking capability, validating the proposed current control method.

Keywords