대한전기학회:학술대회논문집 (Proceedings of the KIEE Conference)
- 대한전기학회 1995년도 추계학술대회 논문집 학회본부
- /
- Pages.456-458
- /
- 1995
고압권선에서 발생하는 부분방전에 의한 초음파 신호 검출
Detection of Ultrasonic Signals by PD at the High Voltage Winding
- Kweon, Dong-Jin (KEPRI) ;
- Kwak, Hee-Ro (Soongsil University) ;
- Chung, Sang-Jin (KEPRI) ;
- Kim, Han-Sang (Soongsil University) ;
- Song, Il-Keun (Soongsil University) ;
- Kim, Kyoung-Wha (Soongsil University)
- 발행 : 1995.11.18
초록
This paper describes a diagnosis of power transformers by on-line detection of ultrasonic signals. Partial discharge in power transformer generates ultrasonic signals. The trend of the ultrasonic signal number can be measured when partial discharge is generated in HV Winding. The trend of the ultrasonic signal number could easily be distinguished by taking moving average. The insulation failure due to partial discharge in transformers can be predicted based in the trend analysis of the number of ultrasonic signals caused by partial discharge.
키워드