• Title/Summary/Keyword: type-3 dry chemical powder

Search Result 4, Processing Time 0.019 seconds

Analysis of the Sedimentation Status Test for Type-3 Dry Chemical Powder with Changes in Internal Pressure of the Dry Chemical Extinguisher (분말소화기의 내부압력 변화에 따른 제3종 분말소화약제의 침강도 시험)

  • Ju-Dal Son;Seo-Young Kim;Ha-Sung Kong
    • Journal of the Korea Safety Management & Science
    • /
    • v.25 no.1
    • /
    • pp.67-74
    • /
    • 2023
  • This study aims to measure sedimentation status change with the changes in internal pressure for dry chemical extinguishers of various use periods and analyze the suitability of the fire extinguishers' performance criteria. When the internal pressure of the fire extinguisher is 0%, 2 out of 10 new dry chemical powders for the 5 elapsed years were noted to be suitable, including 3 recycled dry chemical powders with 5 elapsed years that were found eligible. One out of 10 new dry chemical powders for 10 elapsed years was shown as suitable. Also, one new dry chemical powder for 13 elapsed years was suitable. When the internal pressure of the fire extinguisher was 50%, all 10 out of 10 new dry chemical powders for 5 years, recycled one with 5 elapsed years, and a new one with 10 elapsed years were found to be suitable, while 9 new dry chemical powders for 13 years were shown as suitable. When the internal pressure of the fire extinguisher was normal, new ones with 5 elapsed years, recycled ones with 5 elapsed years, new ones with 10 elapsed years, and new ones with 13 elapsed years were all 10 out of 10 samples noted as suitable. In summarizing the experiment results, it was found that the sedimentation status, one of the fire extinguisher's physical properties experiments, affects the fire extinguisher's performance criteria rather than the change with use periods.

Extinguishing Characteristics of Zeolite adsorbed Dry Chemical Powder (분말 소화약제가 흡착된 제올라이트의 소화 특성)

  • Shin, Changsub;Park, Hojun
    • Journal of the Korean Society of Safety
    • /
    • v.27 no.6
    • /
    • pp.59-63
    • /
    • 2012
  • The use of dry chemical powder has been increased as it can be stored for a long period and sustain in stable condition compared to gas or liquid phase extinguishing agents. A new type of dry chemical powder using Zeolite was produced in the research. Chemical powder was adsorbed into Zeolite 13X, a porous material appearing negative catalytic effect, to create extinguishing powder obtaining core shell structure and measured physical properties and run a small scale fire extinguishment. SEM, XRD, TA analysis was also executed, and extinguishing characteristics were measured by fire extinguishing experiment on oil pool fire. The experiment showed that the average particle size of Zeolite 13X was equivalent, indicating about $3{\pm}1{\mu}m$ and thermal analysis result illustrated that Zeolite 13X showed exothermic reaction peaks at $900^{\circ}C$ due to solid-state transformation. Extinguishing characteristics on oil fire of $NaHCO_3$/Zeolite 13X and $NH_4H_2PO_4$/Zeolite were improved, influenced by adsorbed extinguishing powders on Zeolite 13X and Zeolite 13X that contains high phase transition temperature.

Analysis of the Apparent Specific Gravity for Type-3 Dry Chemical Powder with the Changes in the Internal Pressure of Dry Chemical Extinguisher (분말소화기의 내부압력 변화에 따른 제3종 분말소화약제의 겉보기비중 실험 분석)

  • Ju-Dal, Son;Seo-young, Kim;Ha-sung, Kong
    • The Journal of the Convergence on Culture Technology
    • /
    • v.9 no.3
    • /
    • pp.607-617
    • /
    • 2023
  • This study aims to analyze whether the performance of the fire extinguisher meets the criteria for the apparent specific gravity property test by calculating the change in internal pressure and the use period of the fire extinguisher as a new one with 5 years, recycled one with 5 years, a new one with 10 years, and a new one with 13 years, respectively. As a result of the experiment, when the internal pressure of the fire extinguisher was 0%, the first, second, and third arithmetic mean analysis of the dry chemical extinguisher according to the use period was found to be condemned. When the internal pressure of the fire extinguisher was 50%, it was measured as 130 ml in sample 12-08-new and analyzed as unsuitable. Also, sample 09-09-new of a new dry chemical extinguisher with 13 elapsed years measured 145ml, which was found inappropriate. All other dry chemical extinguishers were analyzed to be suitable. All were noted suitable when having normal internal pressure of the fire extinguisher, except for sample 09-06 of a new dry chemical extinguisher with 13 elapsed years, which was determined to be unsuitable caused by measuring as 131 ml for experimental value. As a result of experiments, some of the apparent specific gravity tests of dry chemical extinguishers from 10 years to 13 years have found that they are unsuitable for the performance of the fire extinguishers due to the massive phenomenon. Accordingly, it is necessary to reduce the endurance period of dry chemical extinguishers from 10 years to 7 years.

Analysis of the Precautionary Measures and Causes on Explosion Accidents of a Old Dry Chemical Powder Extinguisher (노후 분말소화기의 폭발사고 원인과 예방대책에 관한 분석)

  • Lee, Eui-Pyeong
    • Fire Science and Engineering
    • /
    • v.26 no.3
    • /
    • pp.91-99
    • /
    • 2012
  • Fatal injuries and deaths have occurred resulting from the operation or disassembling of a powder extinguishers in Korea. If a rusted powder extinguisher is exploded during operation or disassembling, it rises to the air like a rocket and hits a head, chest, or neck part of an operator, resulting in his (her) death or injury. In this study examines the explosion accident cases of a powder fire extinguisher and analyzes their causes, reactions to explosion, and precautionary measures. And in this paper suggests 1) no using of old fire extinguishers in fire drill or education, 2) education and public information on danger of old fire extinguishers, 3) indication of explosion danger to cartridge-type dry chemical powder fire extinguishers had already placed to buildings etc., 4) obligatory indication of durable years on fire extinguishers, 5) examination for introduction of system that do hydraulic pressure test about fire extinguishers that given period past, 6) construction of system that reclaim old fire extinguishers, 7) construction of system that recycle or reuse old fire extinguishers, and 8) operation of help desk related to old fire extinguishers as precautionary measure of fire extinguisher explosion accidents.