• Title/Summary/Keyword: surge protection

Search Result 215, Processing Time 0.027 seconds

Characteristics of a Home Panel Board with Surge Protection Device (서-지차단장치 내장형 단위세대 분전반의 특성)

  • 이종혁;송재용;이종호;홍경민;길경석
    • Proceedings of the Korean Institute of Information and Commucation Sciences Conference
    • /
    • 2000.05a
    • /
    • pp.480-483
    • /
    • 2000
  • We developed a home electric panel board with surge protection device to protect home electric appliances from transient overvoltages and electromagnetic(EM) noise. In this paper, electrical characteristics of the home electric panel board are described. From the performance test using a combination surge generator standardized in IEC 610004-5, it is confirmed that the proposed home panel board has an excellent surge protection performance. Also, EM noise reduction characteristics of the panel board in ranges from 150 kHz to 30 MHz is estimated by using a network analyser, and the results showed that the panel board has an over 20 45 noise reduction performance.

  • PDF

A Method for Enhancing Data Transmission Performance in the Power-Line Communication Channel with Low-Voltage Surge Protective Devices (저압용 SPD가 설치된 전력선통신에서 데이터전송 성능 향상)

  • Choi, Jong-Min;Jeon, Tae-Hyun
    • Journal of the Korean Institute of Illuminating and Electrical Installation Engineers
    • /
    • v.26 no.2
    • /
    • pp.78-85
    • /
    • 2012
  • Low-Voltage power lines should equip surge protection devices which protect electronic equipments and human lives against lightning and abnormal voltages. Data transmission capacity of the power line is determined by frequency characteristics of the surge protective devices. To analyze the effects of surge protective devices on the data transmission performance, various combinations of installation methods are tested which include ZnO varistor elements that is compatible with class I, class II and class III. The result claims that ZnO varistor for class III is found to be one of the main factors that deteriorates the transmission performance. To overcome this problem a serial connection methed between Gap type SPD and ZnO varistor is proposed. With the proposed scheme, laboratory experimental results show that the data transmission performance can be improved up to 91.9[%] with proper SPD combination.

Lightning Surge Response Characteristics of Non-tripping Type Earth Leakage Breakers for Impulse (충격파 부동작형 누전차단기의 뇌써지 응답 특성)

  • Lee, J.B.;Myung, S.H.;Cho, Y.G.;Chang, S.H.;Kim, J.S.;Kil, G.S.
    • Proceedings of the KIEE Conference
    • /
    • 2002.07c
    • /
    • pp.1688-1690
    • /
    • 2002
  • The unpredictable threat of lightning surge is ever increasing in today's low-voltage power supplies. Thus Surge protection devices for AC mains are more widely used. The false-tripping of the earth leakage breaker (ELB) can be caused by the installation of surge protection devices with MOV. In order to examine the cause of malfunction, the malfunction characteristics of ELBs applied by lightning surge were investigated experimentally. As a result, all of them brought about malfunctions under 7 kV of the impulse voltage. The suitable position of MOV and use of zener diode were suggested to eliminate the problems.

  • PDF

Comparative Study on Water Hammer for Pump Station in High Pressurized Pipes in Kuwait

  • Shim, Kyu Dae;Kang, Yong Suk;Choung, Joon Yeon;Abdellatif, Mohamed;Kim, Dong Kyun
    • Proceedings of the Korea Water Resources Association Conference
    • /
    • 2017.05a
    • /
    • pp.265-269
    • /
    • 2017
  • Because of abrupt changes for velocity in water, transient flow is occurred in practical life. To reduce and avoid the high or low pressure of pipe network system, various surge protection facilities are used to prevent the risk in pipe network system. Especially, we focused on study not only preventing positive and negative pressure but also selecting adequate equipment for high pressurized pipelines. Several critical cases were considered by undertaking a steady state hydraulic study and transient dynamic simulation and we suggested that the surge vessel of various surge protection system was recommended to control high and low pressures on pipeline system in perspective.

  • PDF

Methodology for Risk Assessment for Exposure to Hurricane Conditions

  • Edge, Billy L.;Jung, Kwang-Hyo
    • International Journal of Ocean System Engineering
    • /
    • v.2 no.1
    • /
    • pp.37-49
    • /
    • 2012
  • An analysis of potential flooding by storm surge and wave run-up and overtopping can be used to evaluate protection afforded by the existing storm protection system. The analysis procedure can also be used to evaluate various protection alternatives for providing typhoon flood protection. To determine risk, the storm surges for both historical and hypothetical are compiled with tide conditions to represent high, slack and low water for neap, spring and mid range tides to use with the statistical procedure known as the Empirical Simulations Technique (EST). The EST uses the historic and hypothetical events to generate a large population of life-cycle databases that are used to compute mean value maximum storm surge elevation frequency relationships. The frequency-of-occurrence relationship is determined for all relevant locations along the shoreline at appropriate locations to identify the effect using the Empirical Storm Simulation (EST). To assist with understanding the process, an example is presented for a study of storm surge analysis for Freeport, Texas. This location is in the Gulf of Mexico and is subject to hurricanes and other tropical storms that approach from the Atlantic Ocean.

Failure Prediction of Metal Oxide Varistor Using Nonlinear Surge Look-up Table Based on Experimental Data

  • Kim, Young Sun
    • Transactions on Electrical and Electronic Materials
    • /
    • v.16 no.6
    • /
    • pp.317-322
    • /
    • 2015
  • The metal oxide varistor (MOV) is a major component of the surge protection devices (SPDs) currently in use. The device is judged to be faulty when fatigue caused by the continuous inflow of lightning accumulates and reaches the damage limit. In many cases, induced lightning resulting from lightning strikes flows in to the device several times per second in succession. Therefore, the frequency or the rate at which the SPD is actually exposed to stress, called a surge, is outside the range of human perception. For this reason, the protective device should be replaced if it actually approaches the end of its life even though it is not faulty at present, currently no basis exists for making the judgment of remaining lifetime. Up to now, the life of an MOV has been predicted solely based on the number of inflow surges, irrespective of the magnitude of the surge current or the amount of energy that has flowed through the device. In this study, nonlinear data that shows the damage to an MOV depending on the count of surge and the amount of input current were collected through a high-voltage test. Then, a failure prediction algorithm was proposed by preparing a look-up table using the results of the test. The proposed method was experimentally verified using an impulse surge generator

Hydraulic Characteristic Analysis of Buoyant Flap Typed Storm Surge Barrier using FLOW-3D model (FLOW-3D 모형을 이용한 부유 플랩형 고조방파제의 수리학적 특성 분석)

  • Ko, Dong Hui;Jeong, Shin Taek;Kim, Jeong Dae
    • Journal of Korean Society of Coastal and Ocean Engineers
    • /
    • v.26 no.3
    • /
    • pp.140-148
    • /
    • 2014
  • A storm surge barrier is a specific type of floodgate, designed to prevent a storm surge or spring tide from flooding the protected area behind the barrier. A surge barrier is almost always part of a larger flood protection system consisting of floodwalls, dikes, and other constructions. Surge barriers allow water to pass under normal circumstances but, when a (storm) surge is expected, the barrier can be closed. Among the various means of closing, buoyant flap typed storm surge barrier which was indicated by MOSE project in Italy is chosen for Masan bay protection, and the motion of the surge barrier under the action of storm surge and wave is examined using FLOW-3D, a computational fluid dynamics software analyzing various physical flow processes. Numerical result shows that storm surge barrier is successfully operated under wave height 3 m, and tidal range 2 m.

Surge Protection methods in Railway Signalling system (이상전압으로부터 철도신호설비 보호방안 고찰)

  • Cho, B.K.;Lee, J.H.
    • Proceedings of the KIEE Conference
    • /
    • 2001.10a
    • /
    • pp.285-288
    • /
    • 2001
  • The Railway Signalling Equipment's transformation to Micro-electronic has been caused to the decrease of its introspection against a surge voltage. So, there has been many tries to protect the railway signalling equipment from a surge voltage by using of a various surge protector. In this study, we are trying to draw up the protective plan to prevent this weakness on introspection by analyzing the electric characteristic on such a surge protector and reviewing the way on distributing wires in signalling room.

  • PDF

Study On The Protective Effect of Lightning Surge for Electronic Equipments According to Installation Methods of Surge Protective Device (서지보호소자의 설치방식에 따른 기기의 뇌보호효과 검토)

  • Lee, Suck-Woo;Whang, Kyu-Hyun;Seo, Ho-Joon;Rhie, Dong-Hee
    • Proceedings of the Korean Institute of Electrical and Electronic Material Engineers Conference
    • /
    • 2004.11a
    • /
    • pp.616-619
    • /
    • 2004
  • Lightning surge damages of low voltage equipments in building are increasing due to increase in electrical and communication networks in the information-oriented society. And electronic equipments contained electrical circuits with semiconductor are very weak against lightning surge. The surge protective devices for electronic circuit in electronic equipments and AC power lines are becoming more widely. To achieve effective method of surge protection, there are needs for correlation between lightning surge protective effect of electronic equipment and installation method of surge protective device. This paper describes as a result of experiments for correlation between lightning surge protective effect and installation method of surge protective device.

  • PDF

Discussion On The Protective Effect of Lightning Surge based on The Surge Protective Devices for Low Voltage (저압 피뢰기 적용시 뇌서지 억제 효과 검토)

  • Lee, Suck-Woo;Whang, Kyu-Hyun;Seo, Ho-Joon;Rhie, Dong-Hee
    • Proceedings of the KIEE Conference
    • /
    • 2004.11d
    • /
    • pp.40-42
    • /
    • 2004
  • Electronic equipments made from electrical circuits with small-sized semiconductor are very weak against lightning surge. So, electronic equipments is protected by SPD(surge protective devices) such as Zno varistor. The SPD protect electronic circuit in electronic equipments and AC power lines from the lightning surge. Therefore to achieve effective method of surge protection, there are needs for correlation between lightning surge protective effect and installation method of surge protective device. Therefore this paper describes as a result of experiments for correlation between lightning surge protective effect and installation method of surge protective device.

  • PDF