• Title/Summary/Keyword: series arc waveform

Search Result 11, Processing Time 0.039 seconds

Development of Monitoring Program for Detecting Current and Voltage Signals for Series Arc (직렬아크에 대한 전류 및 전압 신호분석이 가능한 Monitoring Program 개발)

  • Kim, Doo-Hyun;Park, Jong-Young;Kim, Sung-Chul;Lee, Jong-Ho
    • Journal of the Korean Society of Safety
    • /
    • v.25 no.2
    • /
    • pp.29-34
    • /
    • 2010
  • This paper is aimed to develop monitoring software for detecting the characteristics of current and voltage signals for series arc on electric wire. In order to attain this purpose, the characteristics of series arc were analyzed by the current and voltage signals on electric wire which were installed, and also analyzed by the changes of RMS, instantaneous of waveform value in time domain and THD in frequency domain. Monitoring program which analyze the signal was developed by Labview which can analyze in time domain and frequency domain, and save data. Experimental setup for detecting verification of monitoring program was composed loads of a lamp, an electric heater and an electric fan loads which were usually using. Measurement points for detecting verification of monitoring program were selected at both the panel board and the arc generator at the same time. As results of the experiments by monitoring program, the arc current waveform showed the same characteristic in all measurement points of all load. But the arc voltage waveform was different in each measurement point. When arc occurred, the THD of current value increased above 20%. The results of this study will be effectively used in developing the preventive system of electric fire by series arc.

Shoulder Detection of Series Arc-fault Based on Wavelet Transform (웨이브렛 변환을 이용한 직렬 아크고장의 shoulder 검출에 관한 연구)

  • Chung, Young-Sik;Bang, Sun-Bae;Kim, Dong-Wook
    • Proceedings of the KIEE Conference
    • /
    • 2009.07a
    • /
    • pp.2142_2143
    • /
    • 2009
  • Many waveform characteristics of arc signal support the detection of hazardous arc faults. The shoulder is one of main characteristics of arc signal. This paper provide a method for the detection of shoulder from series arc fault based on discrete wavelet transform. The simulation results show that the proposed method is reliable and simple.

  • PDF

Analysis of Voltage, Current and Temperature Signals for Poor Connections at Electrical Connector (커넥터에서 접촉불량 발생시의 전압, 전류 및 온도 신호 특성 분석)

  • Kim, Sang-Chul;Kim, Doo Hyun;Kang, Shin Uk
    • Journal of the Korean Society of Safety
    • /
    • v.29 no.2
    • /
    • pp.12-17
    • /
    • 2014
  • This paper is aimed to analyze the characteristics of simultaneous voltage, current and temperature signals for poor connection on electrical connector. In order to attain this purpose, detected were the current and voltage signals on electric wire with series arc, named arc signals, and also monitored were the changes of RMS, instantaneous value of waveform in time domain and temperature value with video. Two states are made normal state over $5kgf{\cdot}cm$ and poor connections state below $0.5kgf{\cdot}cm$ by screw gage. In the voltage signal case, the voltage drop was increased with which the current was increased. In the current signal case, poor connections at the time interval 1~4A all showed "shoulder", as distinct difference from the normal state shown waveform pattern. In the temperature signal case, poor connections are twice at 1A and five times at 4A in the normal state. The temperature continues insulation of electrical wiring and connector can be carbonized. The results of this study will be effectively used in developing the preventive devices and system for electric fire by poor connections.

Study of Series Arc Waveform Causing Electrical Fire (전기화재를 유발하는 직렬 아크 파형의 고찰)

  • Hwang, Jin-Kwon
    • Proceedings of the Korea Institute of Fire Science and Engineering Conference
    • /
    • 2008.04a
    • /
    • pp.185-188
    • /
    • 2008
  • An apparatus for serial arc in UL 1699 is implemented Current waveforms of arc and a nonlear load are investigated and a method of arc detection can be considered. Introduction of digital signal processing technologies is suggested to correctly detect arcs of electrical fire pyrognostics. This study is expected to be utilized as the basis of such arc detection researches.

  • PDF

The Analysis of Voltage Waveform and Oxidation Growth of Conductor with Series Arc (직렬 아크에 따른 도체의 산화물 증식 및 전압 파형 분석)

  • Choi, Chung-Seog;Kim, Hyang-Kon;Kim, Dong-Ook;Kim, Dong-Woo
    • The Transactions of the Korean Institute of Electrical Engineers P
    • /
    • v.55 no.3
    • /
    • pp.146-152
    • /
    • 2006
  • In order to analyze the characteristics of series arcs that could happen in poor connections of electrical facilities, we made an apparatus which is similar to actual situation. series arcs are generated between copper and copper, copper and bronze, copper and brass, bronze and bronze, and then oxidation growth and voltage waveform were measured. A very small vibration with constant movement is needed to grow oxidation initially, whereas oxidation growth proceeded without a vibration after a certain amount of time. At first, blue white flame was generated initially between copper and copper, and then yellow flame was generated. In case of contact between copper and copper, the length of oxidation growth was about 7.1[mm] in 90[min]. In case of contact between copper and brass, the length of oxidation growth was about 4.3[mm] in 90[min], When bronze is contacted with copper, the lengths of oxidation growth were about 1.4[mm] in 20[min] and 2.7[mm] in 40[min] respectively, and no more oxidation growth was shown after that. In case of contact between brass and brass, the length of oxidation growth was about 1.2[mm] in 90[min], so it was the smallest compared to other cases. When copper is contacted with copper, the current through the load was about 1.6[A] and the power dissipation increased from 19[W] to 31[W]. In case of oxidation growth between copper and brass, the voltage changed from 8.4[V] to 11[V]. However, the voltage drop and the power dissipation between copper and brass were small compared to oxidation growth between copper and copper. When series arcs were generated between bronze and copper, a peak was shown at the beginning of voltage increase, and 40[min] later, oxidation material was not grown any longer. When oxidation growth occurred, voltage waveform showed irregular waveforms with tiny ripples.

Verification of Algorithm for Arc Detection Using High Pass Filter and FFT (고역통과 필터 및 FFT를 이용하여 아크감지 알고리즘 검증)

  • Min-Ho Yoon;You-Jung Cho;Kyoung-Tak Kim;Sung-Hun Lim
    • Journal of the Korean Institute of Electrical and Electronic Material Engineers
    • /
    • v.36 no.5
    • /
    • pp.520-524
    • /
    • 2023
  • An algorithm was developed to detect and block serial arc currents using HPF. The AC series arc problem is that the load current is greater than the fault current and no leakage current occurs. As a solution, an arc detection method utilizing differences in high- frequency amplitudes was developed. HPT was applied to the load current and FFT was applied to eliminate low frequencies. An algorithm has been developed to detect arc waveforms when they exceed a certain value compared to the average of normal waveforms. Using one cycle of data, arc detection is faster and arc accidents are prevented.

Copper Oxide Growing Characteristics of PVC Insulated Wire and Application to the Fire Investigation (비닐절연전선의 산화물 성장 특성과 화재조사에의 적용)

  • Kim, Hyang-Kon;Choi, Chung-Seog;Kim, Dong-Ook;Choi, Hyo-Sang
    • The Transactions of the Korean Institute of Electrical Engineers P
    • /
    • v.56 no.1
    • /
    • pp.37-44
    • /
    • 2007
  • This paper describes characteristics for copper oxide growth of polyvinyl chloride(PVC) insulated wires by series arc. In this experiment, 600V IV wires were used, and characteristics of oxide growth and ignition process were analyzed in case load was 300W, 460W and 600W, respectively. In the result of experiment, covering materials were molten, carbonized and ignited, whereas, oxidized materials were grown in conducting material. During copper oxide was growing, contact voltages and power dissipations increased. When there is copper oxide growth, the waveform of current showed sinusoidal waveform, and the waveform of voltage showed modified waveform. Oxidized materials were heated at about $905^{\circ}C$, surface structure showed irregular shapes, and cross-section showed multiple cracks. And, the results of this experiment were applied to the fire cause analysis of fire evidence collected at the fire scene.

Frequency Domain Analysis of the Linear Load for Series Arc Detection (선형부하의 직렬아크검출을 위한 주파수영역 분석)

  • Kang, Kyoung pil;Bang, Sun Bae;Cho, Younghoon;Choe, Gyu-Ha
    • Proceedings of the KIPE Conference
    • /
    • 2014.07a
    • /
    • pp.524-525
    • /
    • 2014
  • In this paper, we propose algorithm plan variable for detection of DC arc. Changes of surrounding frequencies of harmonic wave is proposed to detect DC arc. To prove validity of these variables, we analyzed frequency based on the measured data and waveform of load current by performing the experiment which generates DC arc by using DC arc generator regulated in UL1699 was carried out.

  • PDF

A Study on Medium Voltage Power Supply with Enhanced Ignition Characteristics for Plasma Torch

  • Jung, Kyung-Sub;Suh, Yong-Sug
    • Proceedings of the KIPE Conference
    • /
    • 2010.07a
    • /
    • pp.242-243
    • /
    • 2010
  • This paper investigates a power supply of medium voltage with enhanced ignition characteristics for plasma torch. Series resonant half-bridge topology is presented to be a suitable ignition circuitry. The ignition circuitry is integrated into the main power conversion system of a multi-phase staggered three-level dc-dc converter with a diode front-end rectifier. The plasma torch rated for 3MW, 2kA and having the physical size of 1m long is selected to be a high enthalpy source in waste disposal system. The steady-state and transient operations of plasma torch are simulated. The parameters of Cassie-Mary arc model are calculated based on 3D magneto-hydrodynamic simulations. Circuit simulation waveform shows that the ripple of arc current can be maintained within ${\pm}10%$ of its rated value under the existence of load disturbance. This power conversion configuration provides high enough ignition voltage around 5KA during ignition phase and high arc stability under the existence of arc disturbance noise resulting in a high-performance plasma torch system.

  • PDF

A Study On Power Factor Correction of SMAW(shielded metal-arc welding) Using Single Phase AC/DC Boost Converter (단상 AC/DC 승압형 컨버터를 이용한 피복 아크 용접기 역률 개선에 관한 연구)

  • Yu Y. J.;Kim L. H.;Kim J. H.;Won C. Y.;Kim Y. R.;Lee S. Y.
    • Proceedings of the KIPE Conference
    • /
    • 2001.07a
    • /
    • pp.556-559
    • /
    • 2001
  • In this paper, we proposed AC/DC boost converter to improve input current harmonic reduction in SMAW(shielded metal-arc welding). The proposed harmonic reduction with the boost converter design and the UC2854 integrated circuit which controls the converter, The topology of welding power supply is made of a pair of boost converter and welder half-bridge IGBT inverter. The voltage arc is modeled by a variable resistance in series with a voltage source. The results has been confirmed by PSIM simulation tool. The simulation results show that input at current is nearly sinusoidal with low harmonic contents and sinusoidal input current waveform at high power factor.

  • PDF