• Title/Summary/Keyword: pool boiling

Search Result 224, Processing Time 0.034 seconds

Pool Boiling Heat Transfer Coefficients of Hydrocarbon Refrigerants on Various Enhanced Tubes (열전달 촉진관에서 탄화수소계 냉매의 풀비등 열전달계수)

  • Park, Ki-Jung;Jung, Dong-Soo
    • Korean Journal of Air-Conditioning and Refrigeration Engineering
    • /
    • v.18 no.12
    • /
    • pp.1017-1024
    • /
    • 2006
  • In this work, pool boiling heat transfer coefficients (HTCs) of five hydrocarbon refrigerants of propylene, propane, isobutane, butane and dimethylether (DME) were measured at the liquid temperature of $7^{\circ}C$ on a 26 fpi low fin tube, Turbo-B, and Thermoexcel-E tubes. All data were taken from 80 to $10kW/m^2$ in the decreasing order of heat flux. The data of hydrocarbon refrigerants showed a typical trend that nucleate boiling HTCs obtained on enhanced tubes also increase with the vapor pressure. Fluids with lower reduced pressure such as DME, isobutane, and butane took more advantage of the heat transfer enhancement mechanism of enhanced tubes than those enhancement ratios of $2.3\sim9.4$ among the tubes tested due to its sub-channels and re-entrant cavities.

Pool Boiling Heat Transfer in Annuli with Closed Bottom

  • Kang, Myeong-Gie;Han, Young-Hwan
    • Nuclear Engineering and Technology
    • /
    • v.34 no.2
    • /
    • pp.165-175
    • /
    • 2002
  • Effects of gap sizes (3.9-44.3 mm) of vertical annuli on nucleate pool boiling heat transfer of water at atmospheric pressure have been obtained experimentally. Through the study, tubes of the closed bottom have been investigated and results are compared with those of a single unconfined tube. According to the results, the annular condition gives much increase in heat transfer coefficient at moderate heat fluxes. The increase is much enhanced 3s the gap size decreases. At the same tube wall superheat (about 3.1 K) the heat transfer coefficient for the least gap size (i.e., 3.9 mm) is more than three times greater than that of the unconfined tube. However, deterioration of heat transfer occurs at high heat flux for confined boiling.

Effect of nanoparticle material for heat transfer enhancement (열전달 향상을 위한 나노물질 코팅재료의 영향에 대한 연구)

  • Jeon, Yong-Han;Kim, Nam-Jin
    • Design & Manufacturing
    • /
    • v.13 no.1
    • /
    • pp.42-47
    • /
    • 2019
  • Nucleate boiling heat transfer is one of the most important phenomenon in the various industries. Especially, critical heat flux (CHF) refers to the upper limit of the pool boiling heat transfer region. Therefore, many researchers have found that CHF can be significantly increased by adding very small amounts of nanoparticles. In this study, the CHF and heat transfer coefficient were tested under the pool boiling state using copper and multi wall carbon nanotube nanoparticles. The results showed that two different types of nanoparticles deposited on the surface of two specimens made of the same material increased the heat flux in the nanoparticles with high conductivity, and there was no difference in the critical heat flux when the same material nanoparticles were deposited on the two different specimen surfaces.

Pool Boiling Heat Transfer Correlation for Pure Refrigerants (순수냉매의 풀비등 열전달 상관식)

  • 고영환;김종곤;송길홍;정동수;김영일
    • Korean Journal of Air-Conditioning and Refrigeration Engineering
    • /
    • v.12 no.10
    • /
    • pp.941-949
    • /
    • 2000
  • Pool boiling heat transfer coefficients (HTCs) of HCFC123, CFC11, HCFC142b, HFC134a, CFC12, HFC22, HFC125 and HFC32 on a horizontal smooth tube have been measured. The experimental apparatus is specially designed to simulate the real heat transfer tube with the use of the secondary fluid of water as a heat source rather than a conventional electric heat source. Data were taken in the order of decreasing heat flux starting at $80 ㎾/m^2\; and \;ending\; at\; 5㎾/m^2\;in\; the\; poo\;l temperature\; at\; 7^{\circ}C$, Test results showed that HTCs of HFC125, and HFC32 are 50~67% higher than those of HCFC22. It is also found that some of the popular pool boiling heat transfer correlations in the literature are not good to predict the HTCs of newly developed alternative refrigerants. A new correlation was developed by a regression analysis which is based upon the consistent data obtained in this study and it showed an excellent agreement with all experimental data having an absolute mean deviation of less than 10%.

  • PDF

Pool Boiling Heat Transfer Coefficient of HFC32/HFC152a on a Plain Surface (평판 표면에서 HFC32/HFC152a 혼합냉매의 풀 비등 열전달계수)

  • Kang, Dong-Gyu;Lee, Yohan;Jung, Dongsoo
    • Korean Journal of Air-Conditioning and Refrigeration Engineering
    • /
    • v.25 no.9
    • /
    • pp.484-492
    • /
    • 2013
  • Nucleate pool boiling heat transfer coefficients (HTCs) are measured with HFC32/HFC152a mixture at several compositions. All data are taken at the liquid pool temperature of $7^{\circ}C$, on a horizontal plain square surface of $9.53{\times}9.53$ mm, with heat fluxes of 10 $kW/m^2$ to 100 $kW/m^2$ with an interval of 10 $kW/m^2$, in the increasing order of heat flux. Test results show that the HTCs of these mixtures are up to 45% lower than those of the ideal HTCs calculated by a linear mixing rule with pure fluids' HTCs, due to the mass transfer resistance associated with non-azeotropic refrigerant mixtures. Pool boiling data show the deduction in HTCs with an increase in GTD of the mixture. The present mixture data agree well with five well known correlations, within 20% deviation.

Hydrodynamic effects of heater lengths on pool boiling critical heat flux (히터 길이가 수조비등 임계열유속에 미치는 수력학적 영향)

  • Su Cheong Park;Do Yeon Kim;Seon Ho Choi;Chang Hoon Lee;Younghun Lim;Chi Young Lee;Yeon Won Lee;Dong In Yu
    • Journal of the Korean Society of Visualization
    • /
    • v.21 no.1
    • /
    • pp.67-73
    • /
    • 2023
  • In the study, pool boing critical heat flux (CHF) was experimentally investigated depending on the length of heaters. A smooth silicon oxide surfaces are used as the boiling surfaces. As the results of pool boiling experiments based on distilled water in ambient pressure condition, the CHF decreased as the length of the heater increased. By the high speed imaging, it was shown that the number of vapor columns increased as the length of the heater increased. Comparing the number of vapor columns and the CHF according to the heater length, the change in the CHF according to the heater length was analyzed based on the hydrodynamic instability.

A Study on the Boiling Heat Transfer of Heat Surface with Fin Array to R-113 (흰열이 있는 전열면의 R-113에서의 비등열전달에 관한 연구)

  • 조시기
    • Korean Journal of Air-Conditioning and Refrigeration Engineering
    • /
    • v.13 no.6
    • /
    • pp.440-447
    • /
    • 2001
  • This study investigate experimentally the effect of in height, thickness, and clearance on the boiling heat transfer. The heat surfaces having copper fin array is tested for pool boiling. The gas-liquid exchange interference is investigated based on fin array clearance. These test results can be applied to the design of tube bundle system. The fin height of 2 mm is found to be effective. Effects of heat transfer promotion reaches the highest level when the fin clearance is 0.5mm. Also, heat flux is increased when the fin thickness is smaller. But0.2 mm fin thickness is highly recommended.

  • PDF

TOWARD MECHANISTIC MODELING OF BOILING HEAT TRANSFER

  • Podowski, Michael Z.
    • Nuclear Engineering and Technology
    • /
    • v.44 no.8
    • /
    • pp.889-896
    • /
    • 2012
  • Recent progress in the computational fluid dynamics methods of two- and multiphase phase flows has already started opening up new exciting possibilities for using complete multidimensional models to simulate boiling systems. Combining this new theoretical and computational approach with novel experimental methods should dramatically improve both our understanding of the physics of boiling and the predictive capabilities of models at various scale levels. However, for the multidimensional modeling framework to become an effective predictive tool, it must be complemented with accurate mechanistic closure laws of local boiling mechanisms. Boiling heat transfer has been studied quite extensively before. However, it turns out that the prevailing approach to the analysis of experimental data for both pool boiling and forced-convection boiling has been associated with formulating correlations which normally included several adjustable coefficients rather than based on first principle models of the underlying physical phenomena. One reason for this has been the tendency (driven by practical applications and industrial needs) to formulate single expressions which encompass a broad range of conditions and fluids. This, in turn, makes it difficult to identify various specific factors which can be independently modeled for different situations. The objective of this paper is to present a mechanistic modeling concept for both pool boiling and forced-convection boiling. The proposed approach is based on theoretical first-principle concepts, and uses a minimal number of coefficients which require calibration against experimental data. The proposed models have been validated against experimental data for water and parametrically tested. Model predictions are shown for a broad range of conditions.

Experimental study of bubble behaviors and CHF on printed circuit board (PCB) in saturated pool water at various inclination angles

  • Tanjung, Elvira F.;Alunda, Bernard O.;Lee, Yong Joong;Jo, Daeseong
    • Nuclear Engineering and Technology
    • /
    • v.50 no.7
    • /
    • pp.1068-1078
    • /
    • 2018
  • Experiments were performed to investigate bubble behaviors and pool boiling Critical Heat Flux (CHF) on a thin flat rectangular copper heater fabricated on Printed Circuit Board (PCB), at various inclination angles. The surface inclination angles were $0^{\circ}$, $45^{\circ}$, $90^{\circ}$, $135^{\circ}$, and $180^{\circ}$. Results showed the Onset of Nucleate Boiling (ONB) heat flux increased with increasing heater orientation from $0^{\circ}$ to $90^{\circ}$, while early ONB occurred when the heater faced downwards ($135^{\circ}$ and $180^{\circ}$). The nucleate boiling was observed to be unstable at low heat flux (1-21% of CHF) and changed into typical boiling when the heat flux was above 21% of CHF. The result shows the CHF decreased with increasing heater orientation from $0^{\circ}$ to $180^{\circ}$. In addition, the bubble departure diameter at the heater facing upwards ($0^{\circ}$, $45^{\circ}$, and $90^{\circ}$) was more prominent compared to that of the heater facing downward ($135^{\circ}$). The nucleation site density also observed increased with increasing heat flux. Moreover, the departed bubbles with larger size were observed to require a longer time to re-heat and activate new nucleation sites. These results proved that the ONB, CHF, and bubble dynamics were strongly dependent on the heater surface orientation.