• Title/Summary/Keyword: multistress

Search Result 4, Processing Time 0.02 seconds

Multistress Life Models of Epoxy Encapsulated Magnet wire under High Frequency Pulsating Voltage

  • Grzybowski, S.;Feilat, E.A.;Knight, P.
    • KIEE International Transactions on Electrophysics and Applications
    • /
    • v.3C no.1
    • /
    • pp.1-4
    • /
    • 2003
  • This paper presents an attempt to develop probabilistic multistress life models to evaluate the lifetime characteristics of epoxy-encapsulated magnet wire with heavy build polyurethane enamel. A set of accelerated life tests were conducted over a wide range of pulsating voltages, temperatures, and frequencies. Samples of fine gauge twisted pairs of the encapsulated magnet wire were tested us-ing a pulse endurance dielectric test system. An electrical-thermal lifetime function was combined with the Weibull distribution of lifetimes. The parameters of the combined Weibull-electrical-thermal model were estimated using maximum likelihood estimation. Likewise, a generalized electrical-thermal-frequency life model was also developed. The parameters of this new model were estimated using multiple linear regression technique. It was found in this paper that lifetime estimates of the two proposed probabilistic multistress life models are good enough. This suggests the suitability of using the general electrical-thermal-frequency model to estimate the lifetime of the encapsulated magnet wire over a wide range of voltages, temperatures and pulsating frequencies.

Longterm Aging Characteristics of Distribution Polymer Housed Surge Arresters by Multistress Accelerated Aging (복합 가속열화를 통한 배전용 고분자 피뢰기의 장기 열화특성 예측)

  • Kim, Ju-Yong;Kwon, Tae-Ho;Park, Chul-Bae;Kim, Joon-Eel
    • Journal of the Korean Institute of Electrical and Electronic Material Engineers
    • /
    • v.20 no.8
    • /
    • pp.691-696
    • /
    • 2007
  • In this study accelerated aging test equipment was developed to simulate domestic weather condition for accelerated aging test of polymer housed distribution surge arresters. Polymer arresters were aged for 3,000 hours by this test equipment and chemical and electrical characteristics analysis of surge arresters were conducted after aging test. In addition, performance assessment of outdoor installed arresters for 3 years was conducted to compare aging effect between accelerated aging test and natural aging. Through this experiment it is verified that the capability of the proposed aging test for simulating natural aging and the housing material and disconnector of domestic polymer arresters can be deteriorated by the long time field operation.

Breakdown Characteristics and Lifetime Estimation of Rubber Insulating Gloves Using Statistical Models

  • Kim, Doo Hyun;Kang, Dong Kyu
    • International Journal of Safety
    • /
    • v.1 no.1
    • /
    • pp.36-42
    • /
    • 2002
  • This paper is aimed at predicting the life of rubber insulating gloves under normal operating stresses from relatively rapid test performed at higher stresses. Specimens of rubber insulating gloves are subject to multiple stress conditions, i.e. combined electrical and thermal stresses. Two modes of electrical stress, step voltage stress and constant voltage stress are used in specimen aging. There are two types of test for electrical stress in this experiment: the one is Breakdown Voltage (BDV) test under step voltage stress and thermal stress and the other is lifetime test under constant voltage stress and temperature stress. The ac breakdown voltage defined as the break-down point of insulation that leakage current excesses a limit value, l0mA in this experiment, is determined. Because the very high variability of aging data requires the application of statistical model, Weibull distribution is used to represent the failure times as the straight line on Weibull probability paper. Weibull parameters are deter-mined by three statistical methods i.e. maximum likelihood method, graphical method and least squares method, which employ SAS package, Weibull probability paper and FORTRAN, respectively. Two chosen models for predicting the life under simultaneous electrical and thermal stresses are inverse power model and exponential model. And the constants of life equation for multistress aging are calculated using numerical method, such as Gauss Jordan method etc.. The completion of life equation enables to estimate the life at normal stress based on the data collected from accelerated aging test. Also the comparison of the calculated lifetimes between the inverse power model and the exponential model is carried out. And the lifetimes calculated by three statistical methods with lower voltage than test voltage are compared. The results obtained from the suggested experimental method are presented and discussed.

Two Factors Failure Model of Oil-Paper Insulation Aging under Electrical and Thermal Multistress

  • Li, Jian;Wang, Yan;Bao, Lianwei
    • Journal of Electrical Engineering and Technology
    • /
    • v.9 no.3
    • /
    • pp.957-963
    • /
    • 2014
  • Converter transformers play important roles in high-voltage direct current transmission systems. This paper presents experimental and analysis results of the combined electrical and thermal aging of oil-impregnated paper at pulsating DC voltages. Breakdown voltages and time-to-breakdown of oil-paper specimens were measured by using short-time and constant-stress tests. The breakdown characteristics of combined electrical and thermal aging on insulation system were discussed. According to the relationship between failure time and aging temperature, the two-parameter Weibull model was improved. On the basis of the competing risk algorithm and the improved Weibull model, the two factors failure model was calculated. And the influence of temperature in the insulation system has been analyzed. This model performs better than the two-parameter Weibull model when both time and temperature are considered as variables in estimating the lifetime of oil-paper insulation.