• Title/Summary/Keyword: low voltage surge

Search Result 115, Processing Time 0.023 seconds

The Protection Effect of Lightning Surge for electronic Equipments According to Installation of Surge Protective Device and Earth Leakage Breaker (서지보호소자와 누전차단기 설치에 따른 기기의 뇌보호 효과)

  • Lee, Suck-Woo;Ko, Yeon-Sung;Yeo, Dong-Goo;Seo, Ho-Joon;Rhie, Dong-Hee
    • Proceedings of the KIEE Conference
    • /
    • 2005.11a
    • /
    • pp.90-92
    • /
    • 2005
  • Lightning surge damages of low voltage equipments in building are increasing due to increase in electrical and communication networks in the information-oriented society. And electronic equipments contained electrical circuits with semiconductor are very weak against lightning surge. The surge protective devices for electronic circuit in electronic equipments and AC power lines are becoming more widely. To achieve effective method of surge protection, there are needs for correlation between lightning surge protective effect of electronic equipment and installation method of surge protective device. This paper describes as a result of experiments for correlation between lightning surge protective effect and installation of surge protective device and Earth Leakage Breaker.

  • PDF

Discussion On The Protective Effect of Lightning Surge based on The Surge Protective Devices for Low Voltage (저압 피뢰기 적용시 뇌서지 억제 효과 검토)

  • Lee, Suck-Woo;Whang, Kyu-Hyun;Seo, Ho-Joon;Rhie, Dong-Hee
    • Proceedings of the KIEE Conference
    • /
    • 2004.11d
    • /
    • pp.40-42
    • /
    • 2004
  • Electronic equipments made from electrical circuits with small-sized semiconductor are very weak against lightning surge. So, electronic equipments is protected by SPD(surge protective devices) such as Zno varistor. The SPD protect electronic circuit in electronic equipments and AC power lines from the lightning surge. Therefore to achieve effective method of surge protection, there are needs for correlation between lightning surge protective effect and installation method of surge protective device. Therefore this paper describes as a result of experiments for correlation between lightning surge protective effect and installation method of surge protective device.

  • PDF

Electrical Characteristics of ZnO Surge Arrester Elements Subjected to the Mixed DC and 60[Hz] AC Voltages (직류+60[Hz] 교류 중첩전압에 대한 ZnO 피뢰기 소자의 전기적 특성)

  • Lee, Bok-Hee;Yang, Soon-Man
    • Journal of the Korean Institute of Illuminating and Electrical Installation Engineers
    • /
    • v.26 no.4
    • /
    • pp.41-47
    • /
    • 2012
  • This paper deals with the electrical characteristics related to power loss, equivalent resistance, and leakage currents flowing through new and deteriorated zinc oxide(ZnO) arrester elements subjected to the mixed DC and 60[Hz] AC voltages. The test specimens were deteriorated by 8/20[${\mu}s$] impulse current of 2.5[kA]. The leakage current-applied voltage($I-V$) characteristic curves of ZnO surge arrester elements were measured as a parameter of the ratio of the peak of 60[Hz] AC voltage to the peak of total voltage. As a consequence of test results, in case of the same applied voltage, the leakage currents flowing through the deteriorated ZnO arrester elements were higher than those flowing through the new ZnO surge arrester elements. The cross-over phenomenon in $I-V$ curves of ZnO surge arrester elements measured as a parameter of the mixed ratio of DC and AC voltages was observed at the low current domain. The effect of DC voltage on the leakage current flowing through ZnO surge arrester elements is pronounced at the same magnitude of test voltages. In addition, the larger the applied number of 8/20[${\mu}s$] impulse current of 2.5[kA] is, the greater the power loss is, in particular, the more severe the power loss increases at higher applied voltages.

Electrical Properties of 18[kV] ZnO Surge Arrester Stressed by the Mixed DC and 60[Hz] AC Voltages (직류+60[Hz]교류 중첩전압에 대한 18[kV] ZnO 피뢰기의 전기적 특성)

  • Lee, Su-Bong;Lee, Seung-Ju;Lee, Bok-Hee
    • Journal of the Korean Institute of Illuminating and Electrical Installation Engineers
    • /
    • v.21 no.10
    • /
    • pp.66-72
    • /
    • 2007
  • This paper describes the characteristics of power loss and leakage currents flowing through new and used 18[kV] zinc oxide(ZnO) surge arrester under the mixed DC and AC voltages. The mixed DC and AC voltage generator of 50[kV] peak was designed and fabricated. The I-V curves of ZnO surge arrester were measured as a function of the voltage ratio K. The I-V curves under the mixed DC and AC voltages lay between the pure DC and AC characteristics, and the cross-over phenomenon in both I-V curves and R-V curves was observed at the low current region. As a result, the increase of DC component in the mixed voltages causes the increase of resistive component of total leakage current of ZnO surge arrester. Also, in the case of same applied voltage, the leakage current flowing through the used ZnO surge arrester was higher than that of the new ZnO surge arrester.

Simulation Method on the Protection Effects of Voltage-Limiting Type SPDs Associated with the Protective Distance (보호거리에 따른 전압제한형 SPD의 보호효과에 대한 시뮬레이션기법)

  • Lee, Bok-Hee;Kim, You-Ha;Ahn, Chang-Hwan
    • Journal of the Korean Institute of Illuminating and Electrical Installation Engineers
    • /
    • v.27 no.7
    • /
    • pp.89-94
    • /
    • 2013
  • This paper presents a method of simulating the protection effects of surge protective devices(SPDs) depending on the protective distance and types of input impedance of load to be protected. In order to analyze the protective performances of voltage-limiting type SPDs associated with the reflection and oscillation phenomena, the terminal voltage across load being protected and the residual voltage of SPDs were simulated by using EMTP model as functions of the protective distance and types of input impedance of loads. As a consequence, SPDs should be installed by taking into account the protective distance and input impedance of loads to achieve reliable protection of electrical and electronic equipment from lightning and switching surges. It is expected that the simulation method proposed in this paper could be practically used in design for installing SPDs in low-voltage distribution systems.

A Measurement of Switching Surge Voltage Using Inverter devices (인버터의 스위칭 서지전압 측정)

  • Kim, Jong-Gyeum;Jeong, Jong-Ho;Lee, Eun-Woong
    • The Transactions of the Korean Institute of Electrical Engineers P
    • /
    • v.53 no.1
    • /
    • pp.14-21
    • /
    • 2004
  • Most adjustable-speed drives (ASDs) designed to operate low voltage induction motors incorporate voltage-source inverters (VSIs), which create motor voltages at high switching frequencies. The motor leads used to connect an ASD to a motor can behave like transmission lines for voltage pulses, which can be reflected at the motor terminals. The resulting oscillatory transient, known as the long-lead effect, can stress and consequently degrade the stator insulation system of a motor. This paper describes the results of tests to 1) determine the correlation between peak motor voltage and the length of motor leads and 2) determine the correlation between peak motor voltage and the switching frequency of the ASD Insulation failures like this usually are caused by voltage surges. Voltage surges are often the result of switching power circuits, lightning strikes, capacitor discharges and solid-state power devices.

Analysis on the effect of RC filter to mitigate transient overvoltage on the high voltage induction motor fed by Multi level inverter (멀티레벨 인버터 구동 고압유도전동기에서 발생하는 과도과전압 저감을 위한 RC필터의 효과분석)

  • Kwon, Young-Mok;Kim, Jae-Chul;Kim, Young-Sung;Lee, Yang-Jin
    • Proceedings of the Korean Institute of IIIuminating and Electrical Installation Engineers Conference
    • /
    • 2005.11a
    • /
    • pp.399-403
    • /
    • 2005
  • In this paper, we analyze on the effect of RC filter to mitigate transient overvoltage on the high voltage induction motor fed by H-bridge cascaded 7-level inverter. The switching surge voltage becomes the major cause to occur the insulation failure by serious voltage stress in the stator winding of high voltage induction motor. The effect of switching surge appears more serious in high voltage induction motor than low voltage induction motor. Consequently, we demonstrated that the RC filter connected to the motor terminals greatly reduces the transient voltage stress md ringing. The results of simulation show the suppression of transient overvoltage at the motor end of a long cable. using EMTP

  • PDF

The electrical properties of in 18kV ZnO surge arrestor with mixed direct and 60Hz Alternating Voltage (중첩전압(직류 +60Hz 교류)에서 18kV 배전용 피뢰기의 전기적 특성)

  • Lee, Bok-Hee;Lee, Seung-Ju;Lee, Su-Bong;Jung, Dong-Cheol;Baek, Young-Hwan
    • Proceedings of the Korean Institute of IIIuminating and Electrical Installation Engineers Conference
    • /
    • 2007.05a
    • /
    • pp.291-294
    • /
    • 2007
  • This paper preserts the characteristics of leakage currents flowing through 18 kV zinc oxide (ZnO) surge arrester under the mixed DC and AC voltages. The I-V curves of ZnO surge arrester were measured as a function of the voltage ratio K The I-V curves under the mixed DC and AC voltages lay between the pure DC and AC characteristics, and the cross-over phenomenon in I-V curves was observed at the low current region As a result, the increase of DC component to mixed voltages causes the increase of resistive component of total leakage current th ZnO surge arrester.

  • PDF

Analysis of inverter switched snubber using N-channel MOS-FET

  • Suzuki, Taiju;Ikeda, Hiroaki;Mizutani, Yoko;Ishikawa, Jinichi;Yoshida, Hirofumi
    • 제어로봇시스템학회:학술대회논문집
    • /
    • 1996.10a
    • /
    • pp.207-210
    • /
    • 1996
  • This paper describes the analysis of the operation of the switched snubber in order to depress the surge voltage in the MOS-FET inverter. In this paper, the N-channel MOS-FET which operates faster than the P-channel MOS-FET was used for the inverter circuit. So, the inverter and switched snubber can operate at high-frequency in the order of MHz. The cause of generating the surge voltage in the high frequency inverter has been cleared, and then how to depress the surge voltage using the switched snubber consisting of an N-channel MOS-FET has been given. Furthermore, described is the power loss within the switched snubber which is made of an N-channel MOS-FET. The inverter having the N-channel MOS-FET used as a switched snubber can drive such a low impedance load such as mega-sonic transducer for a mega-sonic studied cleaner sufficiently.

  • PDF

Effective Installations Technique of Grounding Conductors for Metal Oxide Surge Arrestors (배전피뢰기용 접지도선의 효과적인 설치기법)

  • Lee, Bok-Hui;Gang, Seong-Man;Yu, In-Seon
    • The Transactions of the Korean Institute of Electrical Engineers C
    • /
    • v.51 no.6
    • /
    • pp.253-259
    • /
    • 2002
  • This paper deals with the effects of grounding conductors for metal oxide surge arresters. When surge arresters are improperly installed, the results can cause costly damage of electrical equipments. In particular, the route of surge arrester connection is very important because bends and links of leads increase the impedances to lightning surges and tend to nullify the effectiveness of a grounding conductor. Therefore, there is a need to know how effective installation of lightning surge arresters is made in order to control voltage and to absorb energy at high lightning currents. The effectiveness of a grounding conductor and 18 [㎸] metal oxide distribution line arresters was experimentally investigated under the lightning and oscillatory impulse voltages. Thus, the results are as follows; (1) The induced voltage of a grounding conductor is drastically not affected by length of a connecting line, but it is very sensitive to types of grounding conductor. (2) The coaxial cable having a low characteristic impedance is suitable as a grounding conductor. (3) It is also clear from these results that bonding the metal raceway enclosing the grounding conductor to the grounding electrode is very effective because of skin effect. (4) The induced voltages of grounding conductors for the oscillatory impulse voltages are approximately twice as large as those for the lightning impulse voltages.