• Title/Summary/Keyword: louver

Search Result 134, Processing Time 0.026 seconds

Airside Performance of Convex Louver Fin-and-Tube Heat Exchangers

  • Kim, Nae-Hyun;Oh, Wang-Kyu
    • International Journal of Air-Conditioning and Refrigeration
    • /
    • v.16 no.3
    • /
    • pp.100-107
    • /
    • 2008
  • The heat transfer and friction characteristics of heat exchangers having convex louver fins are experimentally investigated, and the results are compared with those of wave fin counterparts. Eighteen samples (nine convex louver fin samples and nine wave fin samples) which had different fm pitches (1.81 mm to 2.54 mm) and tube rows (one to four) were tested. The convex angle was $11.7^{\circ}$. The j factors are insensitive to fin pitch, while f factors increase as fin pitch increases. The effect of fin pitch on f factor is more significant for the wave fin compared with the convex louver fin. It appears that the complex fin pattern of the convex louver fin induces intense mixing of the flow, and thus reduces the effect of fin pitch. Both the j and f factors decrease as the number of tube row increases. However, as the Reynolds number increases, the effect of tube row diminishes. Comparison of the convex louver fin j factors with those of wave fin reveals that convex louver fin j factors are 18% to 29% higher than those of wave fin. The f factors are 16% to 34% higher for the convex louver fin. The difference increases as fin pitch decreases. Existing correlation fails to adequately predict the present data. More data is needed for a general correlation of the convex louver fin geometry.

Experimental Study of Heat Transfer Characteristics in the Louvered-Fin Type Heat Exchanger (루우버휜형 열교환기의 열전달특성에 관한 실험적 연구)

  • 전창덕;홍주태;이진호
    • Korean Journal of Air-Conditioning and Refrigeration Engineering
    • /
    • v.8 no.1
    • /
    • pp.120-139
    • /
    • 1996
  • Experiment was performed to study the heat transfer characteristics in 27 kinds of 15 : 1 scale models of multi-louverred fin heat exchangers with a wide range of variables(R $e_{Lp}$ =100~1, 800, $L_p$/F$p$=0.3~0.9, $\theta$=20$^{\circ}$~40$^{\circ}$). Thermofoil heaters were used to heat the louver fins and the local average Nusselt number for each louver in the louver array was obtained at constant wall temperature conditions. Correlations are developed to predict the heat transfer characteristics and drag coefficients. Generally, the heat transfer characteristics in the multi-louvered fins is shown to be similar to those of the laminar heat transfer on a flat plate. As the Reynolds number, the louver pitch to fin pitch ratio$L_p$/F$p$and the louver angle($\theta$) increase respectively, the average Nusselt number increases, but the variation of average Nusselt number as a function of the louver angle is smaller than that as a function of the louver pitch to fin pitch ratio. In case of$L_p$/F$p$ <0.5, the average Nusselt number of the 3rd louver is especially lower than the others, it is expected that it is due to the flow structure such as a recirculation flow and a flow separation.

  • PDF

An Experimental Study on the Airside Performance of Fin-and-Tube Heat Exchangers Having Wide Louver Fin (광폭 루버 핀이 장착된 핀-관 열교환기의 공기측 전열 성능에 관한 실험적 연구)

  • Kim, Nae-Hyun
    • Korean Journal of Air-Conditioning and Refrigeration Engineering
    • /
    • v.27 no.5
    • /
    • pp.254-262
    • /
    • 2015
  • Heat transfer rate can be increased by increasing the heat transfer area. In this study, wide louver fin-and-tube heat exchangers with $P_t/P_l=1.03$ were tested and compared with louver fin-and-tube heat exchanger with $P_t/P_l=0.6$. Results show that heat transfer capacities of wide louver samples are larger (9.8% at one row, 13.6% at two row and 4.1% at three row) than those of conventional louver samples. Considering the area ratio of 1.78, the increase of heat transfer capacity is rather small, possibly due to the smaller heat transfer coefficient and fin efficiency of the wide louver sample. The j factor of the louver fin was 67% larger at one row, 42% larger at two row and 52% larger at three row. The f factor of the louver fin was 81% larger at one row, 63% larger at two row and 60% larger at three row. The effect of fin pitch on j and f factors are not pronounced and the j factor decreased as the number of tube row increased.

Numerical Analysis on Flow and Heat Transfer Characteristics in Louver Fin Heat Exchanger (루버휜형 열교환기내 유동 및 열전달 특성에 관한 해석적 연구)

  • 한진호;박상록;김일겸;임장순
    • Korean Journal of Air-Conditioning and Refrigeration Engineering
    • /
    • v.12 no.4
    • /
    • pp.398-403
    • /
    • 2000
  • Numerical analysis was conducted to investigate flow and heat transfer characteristics in louver fin exchanger, which were influenced by louver pitch, fin pitch, louver angle and inlet velocity. Standard $k-\varepsilon$ turbulent modelling was used in this study, and compared with laminar modelling. As a result of this study, Nusselt number became smaller as louver pitch or fin pitch was greater. Drag coefficient became smaller as louver pitch or fin pitch was greater, but it was little affected by inlet velocity.

  • PDF

CORRELATION BETWEEN THE OPENING ANGLE OF A LOUVER AND FLOW RATE FOR THE EFFICIENT CONTROL OF A LARGE FAN (대형 팬의 효율적 유량 조절을 위한 루버 개폐각 상관관계)

  • Noh, T.H.;Lee, S.J.;Chang, S.M.
    • 한국전산유체공학회:학술대회논문집
    • /
    • 2007.10a
    • /
    • pp.272-276
    • /
    • 2007
  • In this paper, we researched a parametric study in flow control system using louver with numerical method. Generally, for the large fans with constant rotational speed, the louver can be used to control the flow rate. The opening and closing of louver can make a some change of flow properties generated by a large fan. To develope the relation between the opening angle of louver and flow rate(or pressure difference), we simulated the flow past the modelled louver installed in a virtual wind tunnel. For the various angles, the mean flow properties are investigated and parameterized with a given boundary condition. The research result can be used directly to design the flow control system of large constant-speed fans, which are often applied to petrolic refinery system.

  • PDF

Numerical Analysis on the Development of a Ventilation Opening Louver for Marine (선박용 환기구 루버 개발을 위한 수치해석)

  • Yi, Chung-Seob;Chin, Do-Hun
    • Journal of the Korean Society of Manufacturing Process Engineers
    • /
    • v.16 no.1
    • /
    • pp.30-35
    • /
    • 2017
  • This study is about distributions of flow in a ventilation system used in a louver for marine. In this study, to describe the flow in the ventilation opening louver, 3-dimensional steady-state turbulence was assumed to govern the equation. The flow field with pressure distribution according to the inlet velocity at the louver types is also compared. Flow analysis was performed for the louver numerical analysis on two types. The numerical analysis results in the louver blade indicated increased flow resistance at type-1.

Improvement for Natural Ventilation Flow inside a Large Factory Building Using Louver-t ype Ventilator (루버를 이용한 대형공장 내부 자 연환기유동 개선에 관한 연구)

  • Kang, Jong-Hoon;Lee, Sang-Joon
    • 한국전산유체공학회:학술대회논문집
    • /
    • 2008.03b
    • /
    • pp.705-706
    • /
    • 2008
  • When heat generated inside a large factory building is not discharged due to a stagnant flow, the working environment of workers becomes worse and the cooling of high-temperature products such as hot-rolling coils is delayed. To investigate the natural ventilation inside a large factory building, experimental studies were carried out using wind-tunnel tests. The scale-down factory building models were placed in an atmospheric boundary layer (ABL) and the mean and fluctuating velocity fields were measured using a particle image velocimetry (PIV) technique. For the prototype factory model, the outdoor air is only entrained into the factory building through the one-third open windward wall, and stagnant flow is formed in the rear part of the target area. In order to improve the indoor ventilation environment of the factory building, three different louver-type ventilators were attached at the upper one-third open windward wall of the factory model. Among the three louver ventilators tested in this study, the ventilator model #3 with the outer louver (${\theta}_o$ = 90$^{\circ}$) and the inner louver (${\theta}_i$ = -70$^{\circ}$) was found to improve the natural ventilation inside the factory building model effectively. The flow rate of the entrained air was increased with aligning the outer louver blades with the oncoming wind and guiding the entrained air down to the ground surface with elongated inner louver blades.

  • PDF

A Daylight Calculation Method for a Louver System Under the Uniform Sky Condition

  • Kim, Kang-Soo;Hwang, Young-Seok
    • Architectural research
    • /
    • v.1 no.1
    • /
    • pp.41-46
    • /
    • 1999
  • The configuration factors in the flux transfer method are applied to calculate daylight factors reaching a station point. To analyze the window equipped with a louver system, geometrical correlation is used for the length shielded by the louver. The space in front of a window is assumed to be an imaginary outdoor space for calculating the luminance of the louver system. The data calculated from this study are compared with SUPERLlTE simulation data and the scale model data. Scale model data are collected on the roof of the Engineering building at Korea University in Seoul under the uniform sky condition.

  • PDF

A Method of Noise Reduction and Improvement in Sound Quality for a Product with the Auto Louver (Auto Louver를 갖는 가전제품의 소음저감 및 음질개선 방법)

  • 한재오;구형모;최원석;김진백
    • Proceedings of the Korean Society for Noise and Vibration Engineering Conference
    • /
    • 2003.11a
    • /
    • pp.1073-1075
    • /
    • 2003
  • 본 글은 가전제품의 안전성, 고급화 및 기능의 차별화를 목적으로 Auto Louver를 설치하는 경우에 있어서 부수적으로 발생하는 2차적 소음에 대해 음질개선 및 소음저감 방법을 소개한다. 실험은 제품의 토출구에 안전망이 설치되고 그 뒤에 Auto Louver를 부착한 자사의 Air Cleaner를 대상으로 실시하였으며, 임의의 공기가 토출되는 조건에서 Auto Louver의 Blade 길이를 줄여 안전망과 Blade 끝단까지의 거리를 이격시킴으로서 1.2KHz-2.5KHz 주파수 대역의 SPL의 저감을 통해 음질을 개선하였고, 이로 인해 토출구로부터 1m 떨어진 위치에서의 소음 측정값을 1.1㏈A의 저감하는 효과를 얻을 수 있었다.

  • PDF

An Analysis on Building Shading Plan for a City Hall considering Energy Saving

  • Kim, Jin Lee;No, Sang Tae
    • KIEAE Journal
    • /
    • v.16 no.2
    • /
    • pp.5-10
    • /
    • 2016
  • Purpose: Recently, many public office buildings which were built by curtain wall increased rapidly, but the results of the investigation of the government, these buildings have been found that the heating and cooling thermal load is high, and showed low energy efficiency. Method: To evaluate the effects by applying outdoor louver and indoor blind, which can control solar radiation in order to reduce the heating and cooling load of public office building which was built by glass curtain wall. The heating and cooling load was calculated via Energyplus, building and outdoor louver, indoor blind were modeled by Google sketchup connected to Energyplus. Result: The results of this study were as follows; the case of applying various outdoor louver, the heating and cooling load all decreased as compared to the case without applying outdoor louver, the case of applying indoor blind, the heating and cooling load decreased as compared to the case without applying indoor blind, but indoor blind showed low energy performance comparing outdoor louver.