Evaluation of Aging on Coil Insulation System for Rotating Machines (고압회전기 절연시스템 열화특성분석을 통한 성능평가)

  • Choi, Young-Chan;Kim, Hong-Je;Seo, Dong-Hyun
    • Proceedings of the KIEE Conference
    • /
    • 대한전기학회 2000년도 하계학술대회 논문집 B
    • /
    • pp.922-924
    • /
    • 2000
  • We worried about the technology difference between our company and the advanced companies at present motor market. Thus we started independently to develop the technology of motor coil insulation system and to accumulate insulation technology data. When we export the electric machines to oversee market. we are asked to set up the insulation system to show our product excellence. We first evaluate the insulation system of our motors to realize higher reliability of high voltage insulation system. Therefore we are possible to do the insulation diagnosis in real site and have accumulated the data related in insulation diagnosis. Thus we have improved the our insulation system. And also these data were used to new product development as very useful data. also will be used the insulation deterioration diagnosis to estimate the remained life time which is very important data for the maintenance management. As the result. we are able to get the our product reliability.

  • PDF

Analysis of Deterioration Characteristics by Filtering Processes at 6.6kV Power Cable Systems in Operation (운전 중인 6.6kV 전력 케이블 시스템의 필터링 과정에 의한 열화 특성 해석)

  • Um, Kee-Hong;Lee, Kwan-Woo
    • The Journal of the Institute of Internet, Broadcasting and Communication
    • /
    • 제14권4호
    • /
    • pp.205-211
    • /
    • 2014
  • With a development of modern industry, demand for electric power is rapidly increasing and the capacity of power transfer is required to become bigger and bigger. At power station, the high-voltage power cable is used as the only method in order to transfer electric power. In this paper, we have analyzed the deterioration characteristics of 6.6kV power cable systems in operation. For the time duration of 2000 days, we have measured the cable in operation in order to extract the data for the deterioration characteristics. By analyzing the data by means of several steps of filtering processes, we could obtain the linear relations of insulation resistances as a function of time. Furthermore, we can verify that the progress characteristics in deterioration process of 6.6kV power cable systems follows the process of heat deterioration.

Properties of Electrical Performance on Stator Coil of Traction Motor by Accelerated lest using Transient Surge (과도서지를 이용한 가속열화 시험법에 따른 견인전동기 고정자 코일의 전기적 특성 변화)

  • 박현준;장동욱;이길헌;최종선;김저우
    • Journal of the Korean Institute of Electrical and Electronic Material Engineers
    • /
    • 제16권9호
    • /
    • pp.783-789
    • /
    • 2003
  • The winding problems of traction motor are the major determinant of motor's life. The root cause of winding failure is gradual deterioration of the insulation due to thermal, electrical, mechanical and environmental stresses. The aging of the insulation reduces the electrical and mechanical strength of the insulation. At same point, a voltage surge or mechanical shock from a traction motor start will fracture or break down the insulation. To achieve the expected life usually requires extensive laboratory evaluation of the insulation systems and the use of accelerated aging tests. There are several nondestructive test available for checking, the condition of motor insulation, the probable extent of aging, and the rate of which aging is taking place. So the insulation characteristics of stator coil were each analyzed by measurement of dielectric loss(tan$\sigma$), capacitance and partial discharge. The method of diagnosis is able to analyze the insulation condition and evaluate the life of the traction motor.

The Properties of Restorative Cement Mortar with Insulation Performance for Improvement of Durability (내구성 향상을 위하여 단열성능이 부여된 단면복구 MORTAR의 물성)

  • Kang, Hyun-Ju;Na, Seung-Hyun;Song, Myong-Shin;Jeong, Eui-Dam;Seo, Byung-Dol
    • Journal of the Korean Ceramic Society
    • /
    • 제47권5호
    • /
    • pp.373-380
    • /
    • 2010
  • In this study, we studied on the durability of restorative cement mortar for deteriorated concrete at complex deteriorated conditions as variation of temperature and of humidities. We made a comparison between restorative materials with insulation function and restorative materials without insulation function in items of compressive and bending strength and permeability of water, durability for carbonation, salt damage, diffusion coefficient of salt at complex deterioration conditions like change of temperature, change of humidity, For insulation, we used close-pore type Alumino-Silicate lightweight aggregate and substituted 12 wt% and 15 wt% out of original restorative cement mortar without insulation function. As a result, it was found that original restorative cement mortar without insulation function fail to meet Korean Standard on polymer modified cement mortar for maintenance in concrete structure, but restorative cement mortar with insulation function is in contentment Korean Standard to meet excellent than restorative materials without insulation function for durability at complex deteriorated conditions.

The Assessment on the Insulation Condition of Generator Stator Windings by a Novel Parameter PDI(Partial Discharge Index) (새로운 파라메타인 부분방전 변화지수에 의한 발전기 고정자 권선의 절연상태 평가)

  • Hwang, Don-Ha;Park, Do-Yeong;Kim, Yong-Ju;Kim, Jin-Bong;Ju, Yeong-Ho
    • The Transactions of the Korean Institute of Electrical Engineers C
    • /
    • 제48권11호
    • /
    • pp.735-741
    • /
    • 1999
  • The monitoring and assessment on the insulation condition of generator stator windings have been an important task of utility companies. The interest for the assessment of insulation condition has been increasing due to the need to keep old generating equipment reliable in order to extend the equipment life and to increase the generating capacity. Even though many developments and research activities for the condition assessment of generator insulation have been performed for decades, the assessment criterion in order to consistently predict the actual insulation condition is still in question. In this paper, the correlation between the parameters and the insulation condition is analyzed through the various non-destructive diagnostic tests in order to establish the assessment criterion on insulation deterioration of generator stator windings. By analyzing the correlation, PDI(Partial Discharge Index) as a novel parameter for the assessment criterion on insulation diagnosis of stator winding is proposed and verified.

  • PDF

Properties of PD and Classification of Defect Patterns in Solid Insulation (고체절연체의 내부결함에 따른 부분방전 특성과 패턴분류)

  • Kang, S.H.;Park, Y.G.;Lee, K.W.;KiM, W.S.;Lee, Y.H.;Lim, K.J.
    • Proceedings of the KIEE Conference
    • /
    • 대한전기학회 1999년도 하계학술대회 논문집 D
    • /
    • pp.1624-1626
    • /
    • 1999
  • PD in defect of solid insulation system is very harmful since It often leads to deterioration of insulation by the combined action of the discharge ions bombarding the surface and the action of chemical compounds that are formed by the discharge. PD can indicate incipient failure, so it has been used to determine degradation of insulation. In this paper. we investigated PD in defects of solid insulation by using statical method and classified PD patterns with surface discharge, electrical tree and void discharge by using Kohonen network. we used peak charge, average discharge power, average discharge current, repetition rate, skewness, kurtosis, QN of the max pulse height vs. repetition rate $H_q(n)$ for analysis and classification.

  • PDF

Evaluation of Insulation Diagnostic Test Reliability for Stator Winding of High Voltage Induction Motor (고압유도전동기 절연특성시험의 신뢰도 평가)

  • Lee, Kwang-Ho;Kim, Hyun-Il;Kwak, Hee-Jin;Oh, Bong-Keun
    • Proceedings of the KIEE Conference
    • /
    • 대한전기학회 2004년도 하계학술대회 논문집 C
    • /
    • pp.1838-1841
    • /
    • 2004
  • This test was performed to assess the correlation between insulation diagnostic tests and breakdown voltage strength of the stator winding of 6.6kV class induction motor in insulation deterioration condition which have been in service for 5 years after being installed in 1998. The insulation diagnostic tests include resistance, polarization index(P.I), dissipation factor(${\triangle}tan{\delta}$), maximum partial discharges(Qmax) and AC breakdown test. we evaluated the correlation between insulation diagnostic test and AC breakdown test for stator winding of high voltage induction motor.

  • PDF

Study on the Characteristics Analysis of Series Arcing at the PVC Insulation Wire for Low Voltage (저압용 비닐절연전선에서의 직렬 아크 특성 분석)

  • Kim, Hyang-Kon;Kim, Dong-Ook;Kim, Dong-Woo;Lee, Ki-Yeon;Choi, Chung-Seog
    • Proceedings of the KIEE Conference
    • /
    • 대한전기학회 2006년도 춘계학술대회 논문집 전기설비전문위원
    • /
    • pp.57-59
    • /
    • 2006
  • In this study, we experimented a deterioration characteristics by series arcing with 600V polyvinyl chloride insulation wire and analyzed the glowing/growing process of copper oxide, waveforms of contact voltage, current, power dissipation and carbonized patterns of insulation. We know that how glowing contacts and surface arcing can decompose PVC insulation and that it is possible for the subsequent series arc to ignite, and burn insulation. We expect that these results are useful for advancing the state-of-the-art in fire protection by Providing a better understanding of how electrical fires can initiate.

  • PDF

Evaluation of Insulation Diagnostic Test Reliability for Stator Winding of High Voltage Induction Motor (고압유도전동기 절연특성시험의 신뢰도 평가)

  • Lee, Kwang-Ho;Kim, Hyun-Il;Kwak, Hee-Jin;Oh, Bong-Keun
    • Proceedings of the KIEE Conference
    • /
    • 대한전기학회 2004년도 추계학술대회 논문집 전기설비전문위원
    • /
    • pp.46-49
    • /
    • 2004
  • This test was performed to assess the correlation between insulation diagnostic tests and breakdown voltage strength of the stator winding of 6.6kV class induction motor in insulation deterioration condition which have been in service for 5 years after being installed in 1998. The insulation diagnostic tests include resistance, polarization index(P.I), dissipation factor(${\Delta}tan{\delta}$). maximum partial discharges(Qmax) and AC breakdown test. we evaluated the correlation between insulation diagnostic test and AC breakdown test for stator winding of high voltage induction motor.

  • PDF

Insulation System and Filter Design for Inverter-Fed Motor (인버터구동 고압전동기 열화특성 분석 및 필터 설계기법 확립)

  • Choi, Young-Chan;Lee, Sang-Dong;Kim, Ik-Mo;Jung, Myung-Gil
    • Proceedings of the KIEE Conference
    • /
    • 대한전기학회 2000년도 하계학술대회 논문집 B
    • /
    • pp.711-713
    • /
    • 2000
  • Recently, the insulation breakdown accident happened at 6.6kV inverter driving motor brings out the reliability decrease to the motor driving system. We need to find the solution with system engineering level. The objectives of this study are developing the appropriate filter for the drive to protect the motor and the insulation system of motor which is driven by inverter. The circuit parameters of cable are calculated by EMTP(Electromagnetic Transient Program) to simulate the system. And we use MATLAB to find the appropriate filter parameter. The simulation and the test results are compared to verify the suitability of the filter parameter. We clarify the cause of the deterioration of the inverter driving motor through the analysis of insulation breakdown accidents. The endurance test scheme and the configuration method of insulation system are established.

  • PDF