서지 전류에 의한 접지계의 과도응답 특성 및 접지저항 비교 (A Comparison on the Resistance and characteristics of Transient response of Grounding Systems under Surge Currents)

  • 신동호;김용;정철희;조대훈;김필수
    • 대한전기학회:학술대회논문집
    • /
    • 대한전기학회 1999년도 추계학술대회 논문집 학회본부 A
    • /
    • pp.222-225
    • /
    • 1999
  • This paper presents the surges response of the grounding systems using frequency domain electromagnetic field analysis software package. The frequency and time domain performance of a building grounding systems subjected to a lighting strike is described and discussed. The computed scalar potentials is presented graphically as a function of spatial coordinates. A double exponential lighting surge current is injected at one corner or the building grounding systems. Time-variant response of rod, mesh and kit grounding systems under impulse currents have been obtained. This paper deals with the results of studies on the time variation of ground resistance in three grounding systems.

  • PDF

저압 수용가 설비에서 누전차단기와 서지방호장치 사이의 보호협조 (Protection coordination between residual current device and surge protective devices in low-voltage consumer's installations)

  • 이복희;김회구;박희열;안창환
    • 조명전기설비학회논문지
    • /
    • 제27권6호
    • /
    • pp.75-81
    • /
    • 2013
  • In this paper, protection coordination between residual current devices and surge protective devices in low-voltage consumer's distribution systems are presented. In the case that a surge protrctive device(SPD) is located on the load side of an residual current device(RCD), when the surge is injected from the source side of the RCD, most of injected surge currents are split into the RCD and the protection coordination between the SPD and RCD is improper, three of 6 specimens experience unintended operation due to test impulse currents. Also when the surges is injected from the load side, a lot of the surge currents is split into the SPD, but a half of test specimens causes nuisance trip. Coordination between SPD and RCD is not valid. When installing SPD, it is important to select SPD after due consideration of the protection voltage level of metal oxide varistor embedded in RCD. It is expected that the results obtained from this work could be useful to improve the protection effects of SPD in low-voltage distribution systems.

영구자석형 횡축형 전동기의 착자기 설계 및 해석 (Design and Analysis of Magnetizer for PM type Transverse Flux-motor)

  • 정수진;강도현;정연호;김동희
    • 대한전기학회:학술대회논문집
    • /
    • 대한전기학회 2002년도 하계학술대회 논문집 B
    • /
    • pp.776-779
    • /
    • 2002
  • This paper describes the magnetizer design of highly saturated magnetic circuit by high external field. The magnetizer is loaded by a capacitor bank with impulse currents to reach high magnetic flux-density(typically 5[T]). Magnetizing current come out from magnetizing system is simulated by analytic method and transient FEM, also field distributions of the magnetizer are analyzed.

  • PDF

임펄스전류에 의한 토양의 절연파괴특성 (Breakdown Characteristics of Soils Caused by Impulse Currents)

  • 이복희;이강수;김회구
    • 조명전기설비학회논문지
    • /
    • 제24권4호
    • /
    • pp.103-109
    • /
    • 2010
  • 이 논문은 동축원통형 전극계에서 임펄스전류에 의한 토양의 절연파괴특성에 관한 것으로 4종의 토양에 대한 절연파괴전압과 전류를 측정하고, 절연파괴를 일으키는 전계의 세기, 절연파괴까지의 지연시간과 전압-전류곡선을 분석하고 검토하였다. 그 결과, 절연파괴전압과 전류 파형은 토양입자의 크기에 의존하며, 자갈과 모래의 절연파괴 전압과 전류 파형은 마사토와 황토의 파형과는 다르게 나타났다. 절연파괴를 일으키는 전계의 세기는 자갈, 모래, 황토, 마사토의 순으로 높았으며, 모든 시료의 전압-전류곡선은 ${\infty}$모양의 교차폐곡선을 나타내었다. 또한 자갈과 모래의 절연파괴까지의 시간지연은 마사토나 황토보다 길게 나타났다. 본 연구 결과는 토양의 이온화를 고려하여 낙뢰전류가 입사되는 접지전극시스템의 과도적 성능의 향상을 위한 설계에 유용한 정보가 될 것이다.

직류+60[Hz] 교류 중첩전압에 대한 ZnO 피뢰기 소자의 전기적 특성 (Electrical Characteristics of ZnO Surge Arrester Elements Subjected to the Mixed DC and 60[Hz] AC Voltages)

  • 이복희;양순만
    • 조명전기설비학회논문지
    • /
    • 제26권4호
    • /
    • pp.41-47
    • /
    • 2012
  • This paper deals with the electrical characteristics related to power loss, equivalent resistance, and leakage currents flowing through new and deteriorated zinc oxide(ZnO) arrester elements subjected to the mixed DC and 60[Hz] AC voltages. The test specimens were deteriorated by 8/20[${\mu}s$] impulse current of 2.5[kA]. The leakage current-applied voltage($I-V$) characteristic curves of ZnO surge arrester elements were measured as a parameter of the ratio of the peak of 60[Hz] AC voltage to the peak of total voltage. As a consequence of test results, in case of the same applied voltage, the leakage currents flowing through the deteriorated ZnO arrester elements were higher than those flowing through the new ZnO surge arrester elements. The cross-over phenomenon in $I-V$ curves of ZnO surge arrester elements measured as a parameter of the mixed ratio of DC and AC voltages was observed at the low current domain. The effect of DC voltage on the leakage current flowing through ZnO surge arrester elements is pronounced at the same magnitude of test voltages. In addition, the larger the applied number of 8/20[${\mu}s$] impulse current of 2.5[kA] is, the greater the power loss is, in particular, the more severe the power loss increases at higher applied voltages.

외부 환경조건에 따른 ZnO 피뢰기의 전기적 특성의 변화 (Changes in Electrical Properties of ZnO Surge Arresters According to Surrounding Conditions)

  • 이승주;이수봉;이복희
    • 조명전기설비학회논문지
    • /
    • 제22권9호
    • /
    • pp.62-68
    • /
    • 2008
  • 이 논문은 ZnO 피뢰기의 외부환경 변화에 따른 전기적 특성을 기술하였다. 뇌임펄스전류에 의한 ZnO 피뢰기의 열화특성을 분석하기 위해 8/20[${\mu}s$], 2.5[kA]의 임펄스전류를 시료에 인가하였다. ZnO 피뢰기의 누설전류를 다양한 외부 온도와 주수 상태에서 상용 주파수 교류 전압을 인가하여 측정하였다. 그 결과 임펄스전류의 인가횟수와 외부 온도가 증가함에 따라 누설전류가 증가하였고, 누설전류의 비대칭성도 뚜렷하였다. 또한 주수 시험에서 ZnO 피뢰기의 외피를 통하여 흐르는 전류는 피뢰기 소자의 누설전류보다 크게 나타났다. 본 연구의 결과는 피뢰기의 감시시스템 성능과 신뢰성 향상의 요소로 적용할 수 있다.

RCD와 SPD의 접속 위치에 따른 보호협조 (Protection Coordination Associated with Connection Location of Residual Current Devices and Surge Protective Devices)

  • 이복희;박희열;신건진;배관영;류춘형;이강희
    • 조명전기설비학회논문지
    • /
    • 제27권3호
    • /
    • pp.100-106
    • /
    • 2013
  • In this paper, in order to analyze lightning impulse response characteristics in combined installations of SPDs and RCDs, surge protection coordination between SPDs and RCDs are experimentally investigated by using the combination wave generator. Six different types of single-phase residual current operated circuit-breakers with integral overcurrent protection for household and similar uses(RCBOs) being present on the domestic market are tested according to KS C IEC 61009-1 standard. As a result, when a class I SPD is located on the source side of an RCBO, all kinds of specimens are able to provide the proper coordination between the SPD and RCBOs without nuisance tripping, unintended operation or damage due to test impulse currents. However, in the case that the class II SPD is located on the load side of RCBOs, a lot of L-N mode injected currents is split into the RCBO, and a few RCBOs are damaged. Coordination between SPDs and RCDs is not valid and a role of SPDs is of no use. When combining SPDs with RCDs, it is necessary to select SPDs and RCDs in consideration of the protection voltage level of metal oxide varistor embedded in RCDs.

3상(相) 유도전동기(誘導電動機)의 토크 및 속도제어(速度制御)에 관한 연구(硏究) (A Study on Torque and Speed Control of Three Phase Induction Motor)

  • 최교호;정석권;양주호
    • 수산해양교육연구
    • /
    • 제7권1호
    • /
    • pp.111-126
    • /
    • 1995
  • In general, the electromagnetic transient phenomenon always exists in induction motor(IM) with the torque change. The control performance of IM is very worse than that of D.C motor owing to this transient phenomenon. So many studies about the elimination methods of the transient phenomenon have been making progress. Interesting methods of them are the Field acceleration method(FAM) and the method of impulse addition on the input voltage at the time point of torque change. In this paper, first, the circuit equation of IM is derived from the phase segregation method. The torque equation consisted of the stator and rotor currents is derived from the solving of the circuit equation. As we well known, the transient terms exist in this the torque equation. The method of impulse addition on the input voltage at the instance of torque change is confirmed theoretically for the elimination of the transient phenomenon. With the base on it, the author proposed a real time algorithm to eliminate the transient terms. The control system is consisted of the PI controller with the feedforward of torque change. The author could confirm that the quick stepwise responses of torque and speed can be obtained from response simulations.

  • PDF

Crowbar 장치를 이용한 최초 단시간뇌격전류 발생기술 및 뇌격전류발생기 개발 (Development of Lightning Current Generator and Technology for Generating the First Short Stroke Lightning Current Using a Crowbar Device)

  • 엄주홍;이태형;권기량;조성철
    • 조명전기설비학회논문지
    • /
    • 제25권1호
    • /
    • pp.93-100
    • /
    • 2011
  • This paper presents a technical study for the first short stroke lightning current generator using a crowbar device. The so-called crowbar-technology is most common to make 10/350[${\mu}s$] impulse currents with high amplitude, and the lightning current generator with crowbar device has an economic advantage than the nominal RLC current generator. But both the operating efficiency and the operating reliability of crowbar spark gap are very important to design the current generator. So, the peaking circuit which consists of small capacitors and a spark gap is applied. And the multi-step coil for controlling the circuit constant at the different test conditions is used. The presented test facility is designed to perform impulse tests with amplitudes up to 50[kA] of 10/350[${\mu}s$].

Statistical study of phase reversal locations on the SC-associated preliminary impulse

  • Sung, Suk-Kyung;Kim, Khan-Hyuk;Cho, Kyung-Suk
    • 한국우주과학회:학술대회논문집(한국우주과학회보)
    • /
    • 한국우주과학회 2008년도 한국우주과학회보 제17권2호
    • /
    • pp.30.3-30.3
    • /
    • 2008
  • In this study, we investigate the magnetic latitude of phase reversal on the sudden commencement (SC)-associated preliminary impulse with 267 SC events using the ground magnetometer data of the IMAGE from 1997 to 2005. During SC event, geomagnetic fields are affected by various currents flowing in the magnetosphere and/or ionosphere. In particular, high-latitude geomagnetic field variations are significantly dominated by the change of SC-associated field aligned current (FAC). Until now, however, there are few studies to examine where the location of the FAC in the ionosphere is and what determines the location of the FAC. The location of the SC-associated FAC can be examined by using magnetometer data obtained from high-latitude stations distributed along the same magnetic meridian. The phase reversal locations are concentrated two regions, ~62 deg (L~4.5) and ~70 deg (L~8.5) in magnetic latitude. If FAC is a result of a mode conversion from fast mode to Alfven mode, then the FAC location could be determine by the duration time of the input energy. When we use the rise time, dT, as the input energy, there is no relationship between dT and the location where the first pulse of SC is reversed. We consider other factors such as local time and solar wind condition.