• Title/Summary/Keyword: ice-storage system

Search Result 173, Processing Time 0.023 seconds

A Study of Storage Type Cooling and Heating System by Heat Pipe (히트파이프를 이용한 축열식 냉.난방 시스템에 관한 연구)

  • Kim, Seong-Sil;Harm, Seong-Chol;Lee, Yang-Ho;Choi, Byoung-Youn
    • Proceedings of the SAREK Conference
    • /
    • 2006.06a
    • /
    • pp.3-8
    • /
    • 2006
  • The heat pump system is attractive alternatives to conventional heating and cooling systems owing to their higher energy utilization efficiency. The thermal loads of commercial and institutional buildings are generally cooling-dominated. In this study have been developed ice storage type heat pump system for cooling and heating by heat pipe. This system was practiced performance test on evaluation criteria for heat storage systems. Accomplished the actual proof examination and looked into the performance of the system. In this study, measurement and analysis of ice storage type heat pump system for cooling and heating by heat pipe. The heat pump unit COP appears 3.05 for cooling and 4.20 for heating. As a result, the method to energy saving and to using a substitute energy actively that is heat pump cooling & heating system is expected by heat pipe. Thermal storage capacity appears $19.5RTH/m^3$ for cooling.

  • PDF

A Field Application Case of Direct Ice Slurry Transporting System for District Cooling (지역냉방용 직접순환식 아이스슬러리 시스템의 현장적용 사례)

  • Yoo, Ho-Seon;Lee, Sang-Hoon;Lee, Yoon-Pyo
    • Korean Journal of Air-Conditioning and Refrigeration Engineering
    • /
    • v.21 no.9
    • /
    • pp.496-504
    • /
    • 2009
  • In order to investigate the feasibility of a direct ice slurry transporting system for the purpose of district cooling, a case study of field application is performed. The research aims include the field measurement of ice packing factor, the performance of coldness delivery, and the branching characteristics of ice slurry. Two representative types of pipe branch are dealt with in this work. For the slurry flow with ice volume fraction of 0.16 or less, the pipe blocking due to aggregation is not observed. Based on the time-wise variation of temperature in the storage tank, a calculating method of ice packing factor is newly developed, which seems to be useful when the brine concentration is unknown. It is confirmed that the mass flow rate of ice slurry per unit cooling load is markedly reduced with increasing the ice content. The pumping power also decreases, but remains unchanged for high ice fractions. The distribution of ice particle before and after branching shows a good uniformity within the range of 5% difference, but yields a unique trend depending on the flow rate.

A study on Characteristics of Heat Flow of Low Temperature Latent Thermal Storage System (저온 잠열 축열조내의 열유동 특성에 관한 연구)

  • Lee, W.S.;Park, J.W.
    • Solar Energy
    • /
    • v.19 no.4
    • /
    • pp.33-43
    • /
    • 1999
  • The study on ice thermal storage system is to improve total system performance and increase the economical efficiency in actual all-conditioning facilities. To obtain the high charging and discharging efficiencies in ice thermal storage system, the improvement of thermal stratification is essential, therefore the process flow must be piston flow in the cylindrical type. With the relation of the aspect ratio(H/D) in the storage tank, the stratification is formed better as inlet flow rate is smaller. If the inlet and the outlet port are settled at the upside and downside of the storage tank, higher storage rate could be obtainable. In case that the flow directions inside the thermal storage tank are the upward flow in charging and the downward in discharging, thermal stratification is improved because the thermocline thickness is maitained thin and the degree of stratification increases respectively. In the charging process, in case of inlet flow rate the thermal stratification has a tendency to be improved with the lower flow rate and smaller temperature gradient in case of inlet temperature, the large temperature difference between inflowing water and storage water are influenced from the thermal conduction. The effect of the reference temperature difference is seen differently in comparison with the former study for chilled and hot water. In the discharging process, the thermal stratification is improved by the effect of the thermal stratification of the charging process.

  • PDF

Real-Time Building Load Prediction by the On-Line Weighted Recursive Least Square Method (실시간 가중 회기최소자승법을 사용한 익일 부하예측)

  • 한도영;이재무
    • Korean Journal of Air-Conditioning and Refrigeration Engineering
    • /
    • v.12 no.6
    • /
    • pp.609-615
    • /
    • 2000
  • The energy conservation is one of the most important issues in recent years. Especially, the energy conservation through improved control strategies is one of the most highly possible area to be implemented in the near future. The energy conservation of the ice storage system can be accomplished through the improved control strategies. A real time building load prediction algorithm was developed. The expected highest and the lowest outdoor temperature of the next day were used to estimate the next day outdoor temperature profile. The measured dry bulb temperature and the measured building load were used to estimate system parameters by using the on-line weighted recursive least square method. The estimated hourly outdoor temperatures and the estimated hourly system parameters were used to predict the next day hourly building loads. In order to see the effectiveness of the building load prediction algorithm, two different types of building models were selected and analysed. The simulation results show less than 1% in error for the prediction of the next day building loads. Therefore, this algorithm may successfully be used for the development of improved control algorithms of the ice storage system.

  • PDF

Characteristic Analysis of the Cooling System Using Ice Slurry Type Heat Storage System (아이스슬러리형 빙축열 시스템을 이용한 냉각 시스템의 특성 분석)

  • Lee, Dong-Won;Lee, Soon-Myung
    • Proceedings of the SAREK Conference
    • /
    • 2006.06a
    • /
    • pp.111-115
    • /
    • 2006
  • To clarify the hydraulic and thermal characteristics of ice slurry which made from 6.5% ethylene glycol-water solution flow in the double tube and plate type heat exchanger, experimental studies were performed. The mass flux and Ice fraction of ice slurry were varied from 800 to $3,500 kg/m^2s$(or 7 to 17 kg/min) and from 0 to 25%, respectively. During the experiment, it was found that the measured pressure drop and heat transfer rate increase with the mass flux and ice fraction; however the effect of ice fraction appears not to be significant at high mass flux region. At the region of low mass flux, a sharp increase in the pressure drop and heat transfer rate were observed depends on mass flux.

  • PDF

A Study on the Energy Storage System Using Air Source Heat Pump for Heating and Cooling (공기 열원을 이용한 축열식 냉난방 시스템 연구)

  • Kim, Ook-Joong;Lee, Kong-Hoon;Seo, Jeong-Kyun
    • Proceedings of the SAREK Conference
    • /
    • 2006.06a
    • /
    • pp.1125-1130
    • /
    • 2006
  • An air source heat pump system producing the ice and water storage energy for cooling and heating of building has been proposed. Cycle design and simulation considering energy balance between heating and cooling capacity has been carried out. The roles of the capacity controlled compressor, refrigerant heating device and air preheating are investigated in detail. System control logic for meeting the predetermined heating capacity when the system is operated at cold climate condition is suggested. Some anticipated problems of the proposed system are also described.

  • PDF

Characteristic of the Formation and Adhesion of Ice on a Cooling Surface by a Stirring Aqueous Solution

  • Kang, Chae-Dong;Seung, Hyun;Hong, Hi-Ki
    • International Journal of Air-Conditioning and Refrigeration
    • /
    • v.14 no.3
    • /
    • pp.110-117
    • /
    • 2006
  • Ice adhesion or cohesion leads to the decrease of the performance of ice making system, especially to dynamic type ice thermal storage system (DISS) which mainly forms ice from the flow of an aqueous solution. The ice adhesion is influenced by various parameters associated with operating or geometric condition. In this study, the influence on an adhesion of ice to the characteristic of cooling surface and to composition of an aqueous solution was fundamentally observed by using batch type cooling device,. a beaker. Three patterns of solution in each beaker were cooled with brine. Moreover, the characteristic of cooling surface on each beaker was distinguished to coating materials. Stirring power as a degree of the ice adhesion was measured. The stirring power to cooling heat transfer rate in each beaker was compared. As a result, the lowest stirring power of 8.9 W with non-adhesion of ice, was shown in the case of the aqueous solution of EG(4) + PG(1.5) + 1,6HD(1.5). in PE coating beaker.

The Experimental Study of Ice Thermal Storage for Falling Film Type - Sprint Coil Type - (스파이럴형 냉동코일을 사용한 유하액막식 빙축열조에서 열전달현상에 관한 실험적연구)

  • Lee, C.M.;Kim, D.H.;Cho, N.C.;Kim, I.G.;Park, S.R.;Choi, K.K.;Yim, C.S.
    • Solar Energy
    • /
    • v.19 no.2
    • /
    • pp.1-8
    • /
    • 1999
  • The heat transfer characteristics of ice storage system of falling film type using sprial coil is investigated. The experimental facilities consisted of a water tank, spiral coils located above the tank, an upper water distributor, and a circulating water pump. Water is distributed uniformally over the spiral coils and it forms falling thin films. In the process of freezing, ice is formed on outside of the spiral coils through recirculation of tank water. In the process of melting, ice is melted with return water from the heat load, while the water is chilled again and drops into the tank. The results of falling film type of ice thermal storage system are as follows. The highly efficient shower flowrates for icing is near $3{\ell}/min$. Icing rates on spiral coils is rosed while brine flowrates is increased. Lower brine temperature is not only increased freezing rates but. also become higher total icing weight and overall heat transfer coefficient. Smaller shower flowrates is obtained lower water temperature on outlet for a long time. The amounts of quantity can be detected more accurately by measuring storage tank weight.

  • PDF

A Study on Estimation of Cooling Load for Effective Control of Ice Thermal Storage System (빙축열 시스템의 효율적인 제어를 위한 냉방부하 예측에 관한 연구)

  • Yoo, Seong-Yeon;Han, Kyu-Hyun;Lee, Je-Myo;Han, Seung-Ho
    • Korean Journal of Air-Conditioning and Refrigeration Engineering
    • /
    • v.20 no.2
    • /
    • pp.128-136
    • /
    • 2008
  • It is necessary to estimate the cooling load of the next day for effective control of ice thermal storage system. In this paper, new methodology is proposed to estimate the cooling load using design parameters of building and predicted weather data. Only six input parameters such as sensible heat coefficient and constant, latent heat coefficient and constant, maximum and minimum temperature are necessary to obtain hourly distribution of cooling load for the next day. Two benchmarking buildings(hospital and research institute) are selected to validate the performance of the proposed method, and the estimated cooling loads in hourly and daily bases are calculated and compared with the measured data for E hospital. The estimated results show fairly good agreement with the measured data for both buildings.