• Title/Summary/Keyword: high voltage cable

Search Result 339, Processing Time 0.031 seconds

A study of Voltage Dmp in Electrical Wiring System for Railway Vehicles (철도 차량 배선의 전압강하에 대한 고찰)

  • Son, Min-Kyu;Jung, Ho-Young;Park, Du-Man
    • Proceedings of the KSR Conference
    • /
    • 2009.05a
    • /
    • pp.959-965
    • /
    • 2009
  • To meet the demand increasing passengers in railway vehicles, railway transportation service companies are increasing the numbers of cars per train-set. Two solutions, Variable train-set formations and Multiple train-set operation, are common way to increase the transportation capability. These kind of long distance train-set can effect train-set command and control system, and sometimes the digital signals using train line from master cabin can not reach to the systems located the other extremity slave car. This is so called Voltage Drop. This phenomenon is originated from the electrical power consumption and electrical cable resistance, and cause to the equipments or cars located end of the electrical cable way, malfunction or abnormal operations. This voltage drop happens not only in train lines but also Battery Power Lines. The purpose of this investigation is to design high reliability railway vehicles by clarifying the possibility of happening these events case by case, by analyzing the reasons, and finally by finding the best solutions.

  • PDF

Diagnostic Test of XLPE Ultra High Voltage Electric Power Cable (XLPE 특고압 전력케이블의 절연 진단)

  • Byun, Doo-Gyoon;Hong, Jin-Woong
    • Proceedings of the Korean Institute of Electrical and Electronic Material Engineers Conference
    • /
    • 2002.05c
    • /
    • pp.122-126
    • /
    • 2002
  • A diagnostic test of 15.4kV cross-linked polyethylene(XLPE) ultra high voltage power cables from generator in the Soyanggang hydro electric power plant was conducted over 3 months, beginning April 2001. According to the results, in the case of the power cables from generator 1, there was little possibility of proceeding rapid1y to failure or defect because the data from diagnosis doesn't indicate any failure, deterioration or partial discharge. However, in the case of the power cables from generator 2, the. polarization index show a slight abnormal condition of the insulator that is not severe, and the deterioration was also identified as not severe. However, the partial discharge had an abnormal condition which was severe.

  • PDF

Partial Discharge Characteristics of Ultra-High Voltage CV Cable Insulators by Electrode Shape (전극형상에 의한 초고압 CV케이블 절연체의 부분방전 특성)

  • Kim Gyun-Sig;Kim Byung-Hyun;Jeong Hyeon-Ki;Cha Kwang-Seok
    • Proceedings of the KSR Conference
    • /
    • 2005.11a
    • /
    • pp.712-717
    • /
    • 2005
  • In this thesis, it is investigated that the effect of the cross linked polyethylene(XLPE) insulator do to breakdown phenomenon by the insertion of the needle and bar electrode into XLPE which is used of electric power cable for the ultra-high voltage. The result of the partial discharge properties in the specimen showed that in case of the insertion of needle or bar electrode into XLPE, the effect of the inner discharge become large when the air void is bigger then the clearance of the electrode of the specimen. The closer the distance between the insulator and needle electrode, it takes less time to the insulation breakdown.

  • PDF

Analysis of Influence for High Frequency Accelerated Aging of XLPE Cable (XLPE Cable의 고주파 가속열화에 대한 영향 분석)

  • Kim, We-Young;Kang, Dong-Sik;Yun, Dae-Hyuk;Park, Tae-Gone
    • Proceedings of the KIEE Conference
    • /
    • 2003.07c
    • /
    • pp.1460-1462
    • /
    • 2003
  • XLPE compound have used for insulation of 22.9 [kV] power cable. XLPE compound is aged for use long time in distribution line. The cause of aging is water tree is happening and growth. Accelerated water tree test method are Accelerated volatge method and high frequency method. In this paper, high frequency accelerated water tree was performed. And the result was analysed AC breakdown voltage and size and number of water trees.

  • PDF

Adhesion properties and Breakdown behaviors of LSR Interface (LSR 계면의 접착특성 및 절연파괴거동)

  • Yoon, Seung-Hoon;Nam, Jin-Ho;Lee, Gun-Ju;Choi, Soo-Geol;Shin, Doo-Sung;Ji, Eung-Seo
    • Proceedings of the Korean Institute of Electrical and Electronic Material Engineers Conference
    • /
    • 2002.11a
    • /
    • pp.232-235
    • /
    • 2002
  • Recently developed liquid silicone rubber (LSR) can be cured by platinum catalyzed additional hydrosilylation mechanism and has the advantage of no byproduct compared to traditional millable peroxide curing silicone rubber. We investigated the characteristics of dielectric breakdown of silicone rubber and adhesion properties between semi-conductive LSR and insulating LSR for high voltage application of pre-molded joint (PMJ). In order to understand the dielectric breakdown characteristics, we used the sheet samples and the paired type rogowski insert electrode system. The breakdown strength and adhesion strength of LSR (E-3) were superior to those of several silicone rubbers. Adhesion strength could be improved by curing at high temperature without post-curing process or enhanced by post-curing process. When LSR (E-3) was cured at $(150^{\circ}C{\times}10min$ semi-conductive )${\times}$ ($175^{\circ}C{\times}10min$ insulation), it showed the high breakdown strength with low standard deviation, and good adhesion strength. In this results, we could apply this process to the fabrication of PMJ without post-curing.

  • PDF

Dielectric Strength Enhancement of Extra High Voltage XLPE Power Cable by Micro-Structural Treatment on Semi-Conductive Interface (XLPE 계면에서의 라멜라 구조 제어 및 전기적 특성)

  • Cho, Dae-Hee;Shim, Sung-Ik;Youn, Bok-Hee;Lee, Sang-Jin
    • Proceedings of the Korean Institute of Electrical and Electronic Material Engineers Conference
    • /
    • 2004.11a
    • /
    • pp.293-296
    • /
    • 2004
  • 초고압 케이블의 절연물질로 널리 사용되고 있는 가교 폴리에틸렌의 전기적 특성은 라멜라 결정 조직의 밀도와 라멜라 조직의 성장방향과 밀접한 관련이 있는 것으로 알려지고 있다. 본 연구에서는 반도전 물질에 2종의 첨가제를 이용하여 처방한 3종의 반도전 컴파운드에 대하여 시편 제작 조건에 따른 미세 조직을 제어하여 폴리에틸렌의 미세 조직을 변화시킴으로써, 라멜라 조직이 전기적 특성에 미치는 영향을 분석하였다. 전기적 특성은 AC 절연파괴 전압을 측정하였으며, 미세 조직 변화를 조사하기 위하여 TEM 이미지 분석 통하여 라멜라 밀도를 통계적으로 정성 분석하여 상관관계를 규명하였다.

  • PDF

The Effect of Discoloration on the Electrical Properties of Alumina Filled Epoxy (Alumina Filler가 충진된 에폭시 경화물(硬化物)의 변색(變色)이 전기적(電氣的) 특성(特性)에 미치는 영향(影響))

  • Hahn, K.M.;Kim, D.W.;Oh, M.W.;Kweon, H.S.;Kim, Y.S.
    • Proceedings of the Korean Institute of Electrical and Electronic Material Engineers Conference
    • /
    • 1993.05a
    • /
    • pp.59-62
    • /
    • 1993
  • This Paper studies on thermal oxidation of alumina filled epoxy network polymer used in Extra-High voltage application. The thermal oxidation of surface has investigated by yellow index variation and various electrical properties which are surface resistivity, tracking resistance and AC dielectric strength are estimated by yellow index.

  • PDF

A field trial of helically wrapping fiber optic cable onto existing 154KV Phase conductor. (전력선을 이용한 광케이블 현장 실증 시험)

  • Shin, Keon-Hak;Lee, Won-Bin;Cho, Hong-Keun
    • Proceedings of the KIEE Conference
    • /
    • 1987.11a
    • /
    • pp.143-146
    • /
    • 1987
  • Fiber optics provide a solution to the problems at interference, capacity and reliability in communication. Approximately 20 kilometera of a six-fiber, multimode, longwave($1.3{\mu}m$), graded index silica glass fiber optic cable was helically wrapped around a phase conductor at a Korea Electric Power Corporation(KEPCO) 154KV transmission line. This paper presents an economic comparison of several fiber optic cable installation alternative and discusses the characteristics at the helically wrapped fiber cable, as well as the entire installation, including high voltage phase-to-ground (PTG) end termination, and splicing. The fiber link was installed for the field trial and practical use with overhead composite optical fiber cable which installation performed a few years earlier some other location and is intended to accommodate not only telephone but also supervisory Control and Data Acquisition(SCADA), protective relaying, and telemetry functions.

  • PDF

Dielectric Strength Enhancement of Extra High Voltage XLPE Power Cable by Micro-Structural Treatment on Semi-Conductive Interface (초고압 XLPE 케이블 계면 미세조직 제어에 의한 절연 내력 향상)

  • Cho, Dae-Hee;Shim, Sung-Ik;Yeoun, Bok-Hee;Lee, Sang-Jin
    • Proceedings of the KIEE Conference
    • /
    • 2004.11a
    • /
    • pp.205-208
    • /
    • 2004
  • 초고압 케이블의 절연물질로 널리 사용되고 있는 가교 폴리에틸렌의 전기적 특성은 라멜라결정 조직의 밀도와 라멜라 조직의 성장방향과 밀접한 관련이 있는 것으로 알려지고 있다. 본 연구에서는 반도전 물질에 2종의 첨가제를 이용하여 처방한 3종의 반도전 컴파운드에 대하여 시편 제작 조건에 따른 미세 조직을 제어하여 폴리에틸렌의 미세 조직을 변화시킴으로써, 라멜라 조직이 전기적 특성에 미치는 영향을 분석하였다. 전기적 특성은 AC 절연파괴 전압을 측정하였으며, 미세조직 변화를 조사하기 위하여 TEM 이미지 분석 통하여 라멜라 밀도를 통계적으로 정성 분석하여 상관관계를 규명하였다.

  • PDF

The Jointing Methode for HVDC Submarine Cable (HVDC 해저케이블 접속절차)

  • An, Y.H.;Jang, T.I.;Jeon, D.H.;Hwang, K.C.;Jung, G.J.;Kim, J.N.
    • Proceedings of the KIEE Conference
    • /
    • 2007.07a
    • /
    • pp.748-749
    • /
    • 2007
  • HVDC(High Voltage Direct Current) is an underwater cable between Jeju Island and Haenam in main land and supplies approximately 50% of electrical usage in Jeju Island. If there is any power failure due to HVDC, it will cost approximately 50,000 US dollars per day including Thermal Electrical Generation. Therefore it is absolutely necessary to recover the problem in rapid timely basis. In conclusion, jointing methode of HVDC cable is needed urgently to upgrade current HVDC underwater cable repair technique in Korea to minimize the cost and time factors.

  • PDF