• Title/Summary/Keyword: heat-absorption

Search Result 947, Processing Time 0.031 seconds

Performance Experiment of Generator for Household Absorption Chiller and Heater (가정용 흡수식 냉난방기 개발을 위한 재생기 성능실험)

  • Yu, Sun-Il;Kwon, Oh-Kyung;Yoon, Jung-In
    • Transactions of the Korean Society of Mechanical Engineers B
    • /
    • v.23 no.10
    • /
    • pp.1347-1354
    • /
    • 1999
  • Recently, the markets of the air conditioner are enlarging. The market size will reach 2.0 billion won in 2000. Electric heat pumps have been utilized as main residential air conditioners. especially in Korea. They cause a surge up electric power demand during summer. Moreover, the use of HCFCs and HFCs causes serious problem to the global environment such as global warming and ozone layer destruction. Absorption chiller and heater could solve such problems. It was built and tested for analyzing the performance of the generator for absorption chiller and heater. Experiment was done with a high temperature generator, a low temperature generator, heat exchangers, a condenser and a solution tank. It was tested that the double effect series flow cycle with two kinds of solution cycle. Solution cycle B showed better than solution cycle A. Two kinds of heat exchanger were used, where one's heat transfer area is bigger than the other. Bigger one increased a little performance of absorption chiller and heater. But it was not economical. From this study, we got that the coefficient of performance(COP) is 0.82 and the capacity is 7.24 kW for an absorption chiller and heater.

Coupled Heat and Mass Transfer during the Absorption of Water Vapor into LiBr-H2O Liquid Solution Flowing down the Outside of the Horizontal Cylinder (수평원관상의 LiBr-수용액에 수증기가 흡수될때의 열 및 물질전달)

  • Lee, K.S.;Seo, S.C.;Kim, Y.I.;Park, D.K.
    • The Magazine of the Society of Air-Conditioning and Refrigerating Engineers of Korea
    • /
    • v.17 no.2
    • /
    • pp.140-149
    • /
    • 1988
  • The problem of heat and mass transfer accompanying the absorption of water vapor into LiBr-$H_2O$ liquid solution flowing over the outside of the horizontal cylinder was theoretically studied to understand the absorption process occuring in the absorber of the absorption heat pump. Numerical results are presented for various quantities of interest relating to temperature, concentration, heat flux and mass flux. Also, the effects of mass flowrate, initial average velocity, and the radius of the cylinder were investigated.

  • PDF

Rectification Characteristic of Packing Materials in the Packed-type Rectifier of $NH_3/H_2O$ Absorption Heat Pump (암모니아 흡수식 열펌프 충전식 정류기의 정류 특성에 관한 연구)

  • 김돈수;윤상국
    • Korean Journal of Air-Conditioning and Refrigeration Engineering
    • /
    • v.14 no.10
    • /
    • pp.775-780
    • /
    • 2002
  • An experimental study on the characteristics of several kinds of packing materials was carried out in order to get the optimum design data for the packed-type rectification system of an NH$_3$/$H_2O$ GAX absorption heat pump. Several suitable packing materials were examined and the bulk of steel wire was shown as the most effective packing material in rectifier. The optimum volumetric ratio of packed steel wire in rectifier was obtained as around 36%. The performance results can be adapted in rectifier design of absorption heat pump.

Analysis of Heat and Mass Transfer on Helical Absorber (헬리컬 흡수기의 흡수 열물질전달 해석)

  • Gwon, O-Gyeong;Im, Jong-Geuk;Yun, Jeong-In;Kim, Seon-Chang;Yun, Jae-Ho
    • Transactions of the Korean Society of Mechanical Engineers B
    • /
    • v.24 no.11
    • /
    • pp.1428-1436
    • /
    • 2000
  • The absorption of vapor involves simultaneous heat and mass transfer in the vapor/liquid system. In this paper, a numerical study for vapor absorption process into LIBr-H$_2$O solution film flowing over helical absorber has been carried out. Axisymmetric cylindrical coordinate system was adopted to model the helical tube and the transport equations were solved by the finite volume method. The effects of operating conditions, such as the cooling water temperature. the system pressure, the film Reynolds number and the solution inlet concentration have been investigated in view of the absorption mass flux and the total absorption mass flux and the total absorption rate. The results for the temperature and concentration profiles, as well as the local absorption mass flux at the helical absorber are presented. It is shown that solution inlet concentration affected other than operation conditions for a mass flux.

An Effect on the Solution Crystallization Temperature Difference and Cooling Capacity of the Absorption Chiller by a Solution Cooler in the Absorber (흡수기내 용액 냉각기가 흡수식 냉동기의 용액 결정화 온도차와 냉각 용량에 미치는 효과)

  • Chin, Sung-Min;Lee, Jae-Heon;Jurng, Jong-Soo
    • Proceedings of the KSME Conference
    • /
    • 2003.04a
    • /
    • pp.1518-1523
    • /
    • 2003
  • The objective of the present work is to investigate an effect on the solution crystallization temperature difference and the cooling capacity of the absorption chiller by a solution cooler in the absorber. The cooling capacity of the absorption chiller can be higher, with the enhanced performance of the solution heat exchangers. But, because the solution crystallization temperature difference becomes smaller at the absorber inlet, the heat capacity of the solution heat exchangers might be limited by the danger of crystallization, which can cause the serious damages. In this paper, the heat capacity ratio of the solution cooler is defined as the ratio of the heat capacity of the solution cooler to that of the absorber. If it becomes larger in the additional type solution cooler, the solution crystallization temperature difference is augmented and the cooling capacity is also increased.

  • PDF

An investigation of absorption phenomena in the horizontal staggered tube absorber for various LiBr solution flow rates (LiBr용액량 변화에 따른 수평다관 흡수기의 특성 연구)

  • Kwon, Yul;Yoon, Sang-Guk
    • Korean Journal of Air-Conditioning and Refrigeration Engineering
    • /
    • v.11 no.3
    • /
    • pp.332-338
    • /
    • 1999
  • An experimental study of absorption phenomena of water vapor into LiBr solution was carried out to find out the optimum solution flow rate. The staggered bundle of horizontal absorption tubes, which are the same configuration as the commercial heat pump, were tested. The results showed that the heat transfer and absorption rate were enhanced with the increase of LiBr solution flow rate. Those values for different absorber pressures showed the same qualitative trends. The optimum flow rate of solution was obtained as three times of the designed flow rate.

  • PDF

A Study on the COP Improvement of Absorption Chillers by Recovering Heat from the Condenser (응축기 배열회수에 의한 흡수식 냉동기의 고효율화에 관한 연구)

  • Park, Chan-Woo
    • Korean Journal of Air-Conditioning and Refrigeration Engineering
    • /
    • v.18 no.9
    • /
    • pp.738-744
    • /
    • 2006
  • In order to utilize the condensation heat of refrigerants in condenser on the absorption chiller system, the solution cooled condenser (SCC) was proposed using the weak solution of absorber as a cooling medium. The increase of COP with the increase of UA of the solution cooled condenser was approximately 0.009 in maximum with single effect one, and is about maximum 0.008 in occasion of double effect one with series flow compared to that without. In the case of heat exchanger, effectiveness is about 0.85, it's increments are 0.008 and 0.0072, respectively. And solution cooled condenser is more effective device in the single effect absorption system than double effect system for the principle of operation. On the other hand, as the solution split ratio increases when the value of UA is fixed, COP is increased and as the solution split ratio increases when the value of UA is fixed, COP is increased. If the flow rate of cooling water or the value of UA is reduced in order to increases the heat recovery of solution cooled condenser, heat recovery of solution cooled condenser is increased a little but COP is decreased as the system pressure is increased.

Comparison Between Two Solar Absorption Cooling System Using Single Effect and Single Effect/Double Lift Cycle (일중효용 사이클과 일중효용/2단승온 사이클을 이용한 태양열 흡수식 냉방시스템의 비교)

  • 정시영;이상수;조광운;백남춘
    • Korean Journal of Air-Conditioning and Refrigeration Engineering
    • /
    • v.12 no.3
    • /
    • pp.267-276
    • /
    • 2000
  • A numerical study has been carried out to find out the optimal design condition of a solar absorption cooling system. The system was composed of solar collectors and an absorption chiller with LiBr/water The System performance with commercial single effect(SE) cycle and a new single effect/double lift(SE/DL) cycle utilizing low temperature hot water was calculated and compared. It was found that the required solar collector area grew exponentially as the overall heat loss coefficient of solar collectors increased. For instance, the required area for cooling capacity of 1 USRT was $17m^2$ if heat loss coefficient was 4 W/$m^2\;cdot\;K$. If heat loss coefficient was doubled($8\;W/m^2\;cdot\;$K), the required collector area was increased by 6 times($100m^2$) .It was also found that the SE-cycle as the heat loss coefficient of solar collectors increased. Generally, a SE/DL-cycle seems to be more advantageous than a SE-cycle if loss coefficient of solar collector is greater than 4 W/$m^2\;cdot\;K$.

  • PDF

Heat transfer and pressure drop characteristics of plate heat exchangers for absorption application (흡수식 시스템의 용액열교환기용 판형열교환기의 열전달 및 압력강하 특성 실험)

  • Kim, Hyun-Jun;Kim, Jung-Hwan;Kim, Sung-Soo;Jeong, Jin-Hee;Kang, Yong-Tae
    • Proceedings of the SAREK Conference
    • /
    • 2005.11a
    • /
    • pp.347-352
    • /
    • 2005
  • The objectives of this paper are to study the characteristics of heat transfer and pressure drop in plate heat exchangers for absorption applications, and to quantify the effect of mass flow rate, solution concentration, and geometric conditions such as chevron angle on the heat transfer coefficient and pressure drop in the plate heat exchangers. The working fluid is $H_2O$/LiBr solution with the LiBr concentration range of 53.2 - 62.5 % in mass. The results show that the overall heat transfer coefficient increases linearly with increasing Re. The heat transfer rate increases with increasing the chevron angle while it does not significantly depend on the LiBr concentration. The pressure drop also increases with increasing the chevron angle. The effect of the chevron angle on the pressure drop is more significant than that of the concentration.

  • PDF

Experiment on Heat Transfer and Absorption Performance Enhancement for Binary Nanofluids (NH3/H2O + Nano-Particles) (이성분 나노유체 (NH3/H2O + 나노입자)의 열전달 및 흡수성능 촉진실험)

  • Lee, Jin-Ki;Jung, Chung-Woo;Kang, Yong-Tae
    • Transactions of the Korean Society of Mechanical Engineers B
    • /
    • v.32 no.9
    • /
    • pp.669-675
    • /
    • 2008
  • The objectives of this paper are to examine the effect of nano-particles on the pool type absorption heat transfer enhancement and to find the optimal conditions to design a highly effective compact absorber for ammonia/water absorption system. The effect of $Al_2O_3$ nano-particles and carbon nanotube(CNT) on the absorption performance is studied experimentally. The experimental ranges of the key parameters are 20% of ammonia concentration, $0{\sim}0.08\;vol%$ (volume fraction) of CNT particles, and $0{\sim}0.06 \;vol%$ of $Al_2O_3$ nano-particles. For the ammonia/water nanofluids, the heat transfer rate and absorption rate with 0.02 vol% $Al_2O_3$ nano-particles were found to be 29% and 18% higher than those without nano-particles, respectively. It is recommended that the concentration of 0.02 vol% of $Al_2O_3$ nano-particles be the best candidate for ammonia/water absorption performance enhancement.