LiBr용액량 변화에 따른 수평다관 흡수기의 특성 연구

An investigation of absorption phenomena in the horizontal staggered tube absorber for various LiBr solution flow rates

  • 권율 (한국해양대학교 대학원 기계공학과) ;
  • 윤상국 (한국해양대학교 냉동공조공학과)
  • 발행 : 1999.05.01

초록

An experimental study of absorption phenomena of water vapor into LiBr solution was carried out to find out the optimum solution flow rate. The staggered bundle of horizontal absorption tubes, which are the same configuration as the commercial heat pump, were tested. The results showed that the heat transfer and absorption rate were enhanced with the increase of LiBr solution flow rate. Those values for different absorber pressures showed the same qualitative trends. The optimum flow rate of solution was obtained as three times of the designed flow rate.

키워드