• Title/Summary/Keyword: harmonic filter

Search Result 652, Processing Time 0.025 seconds

Design of harmonic reduction equipment for load system (부하설비의 고조파 저감장치 설계)

  • Son, Jae-Hyun;Cho, Yang-Heang;Kim, Je-Hong
    • Proceedings of the KIEE Conference
    • /
    • 2006.10b
    • /
    • pp.224-228
    • /
    • 2006
  • The aim of this study is to design a passive filter for the elimination of harmonics. For this design, the harmonics wave generating from the six pulse rectifier was measured and its characteristics were analyzed. We also calculated the quantity of harmonic current by changing the system operational conditions. According to this field data and calculated results, we determined the elements of the passive filter. The simulation and experimental results indicate the efficiency of designed passive filter.

  • PDF

Reduction of Current Harmonic Occurred form between Uninterruptible Powers Supply and Rectifier Load (정류기 부하와 무정전전원장치 사이에 발생되는 Current Harmonic 저감)

  • 곽철훈;반한식;최규하;목형수
    • Proceedings of the KIPE Conference
    • /
    • 1999.07a
    • /
    • pp.41-44
    • /
    • 1999
  • The main purpose of the UPS is to supply independent and stable power to connected equipment. In installing and operating the UPS system, songle module, three phase UPS in more benefit than multi module, songle phase UPS in the point of volume and cost. However, when supplying Rectifier with output power form three phase UPS, by connecting auto-transformer, occurred harmonic and ripple current makes output filter damaged and leads to nonlinear current coasted by unbalance load. Therefor, in this paper the aim of concentring compound-wound transformer and harmonic filter is supplying liner current by reducing harmonic and ripple current and improving unbalance in voltage and distortion in current wave.

  • PDF

Modified Microstrip Filters Improving the Suppression Performance of Harmonic Signals (고조파 감쇠특성을 향상시킨 변형된 마이크로스트립 여파기)

  • 김봉수;이재욱;송명선
    • The Journal of Korean Institute of Electromagnetic Engineering and Science
    • /
    • v.13 no.10
    • /
    • pp.1054-1060
    • /
    • 2002
  • In this paper, a new parallel-coupled-line microstrip BPF(BandPass Filter) improving the suppression performance of 2nd harmonic signals is studied. Using the consecutive pattern in coupled-line, the desired passband performance is improved and harmonic passband signal is rejected. Recalculation of classical filter design parameters(space-gap between lines, line widths and lengths) is not required. That is, after using the classical design methodology for parellel-coupled-line BPF, new filters can be easily realized by inserting periodic patterns in coupled-line. To investigate the validity of this novel technique, order-3 Butterworth BPF centered at 2.5 GHz with a 10 % FBW(Fractional Bandwidth) and order-5 Chebyshev BPF centered at 10 GHz with a 15 % FBW were used. When five and three square grooves are used, over 30 dB harmonic suppression at 2nd harmonic is achieved in simulation and experiment.

Ultrasound Harmonic Imaging Method based on Harmonic Quadrature Demodulation (하모닉 직교 방식의 초음파 고조파 영상화 기법)

  • Kim, Sang-Min;Song, Jae-Hee;Song, Tai-Kyong
    • Journal of Biomedical Engineering Research
    • /
    • v.30 no.1
    • /
    • pp.79-88
    • /
    • 2009
  • A harmonic quadrature demodulation method to extract the second harmonic component from focused ultrasound signals after a single transmit-receive event is proposed. In the proposed method, the focused ultrasound signal is converted into baseband inphase and quadrature components by multiplying with sine and cosine signals both having twice the center frequency of the transmitted signal and filtering the two modulated signals. The quadrature component is then passed through a Hilbert filter to be added to the inphase component, which leaves only the envelope of the second harmonic component. A novel phase estimation technique is employed in the proposed method to avoid the phase mismatch between the focused signal and the two modulating signals. The proposed method is verified through both theoretical analysis and computer simulations. It is shown that compared to the pulse inversion scheme the proposed method provides almost the same results for stationary targets and significantly improved harmonic to fundamental ratio for moving targets.

A Study on the Series and Parallel Resonant Filters for Harmonic Currents Reduction of Nonlinear Loads (비선형부하의 고조파전류 저감을 위한 직렬 및 병렬 동조필터에 관한 연구)

  • 김경철;강윤모;백승현;김종욱
    • Journal of the Korean Institute of Illuminating and Electrical Installation Engineers
    • /
    • v.17 no.6
    • /
    • pp.113-118
    • /
    • 2003
  • This paper characterizes typical nonlinear loads into two types of harmonic sources, i.e., harmonic voltage source and harmonic current source. A series resonant filter is very effective in harmonic reduction for harmonic voltage source type of nonlinear loads such as personal computer loads with smoothing dc capacitors. A parallel resonant filter is suited for current source type of nonlinear loads such as ac drives with smoothing dc reactors. General compensation characteristics and comparison of series and parallel resonant filters are given analytically and experimentally. Compliance with IEC Std 1000-3-2 has been evaluated for limiting harmonic distortion.

Performance Analysis for Passive Filter Considering Allowable Limits of Tolerance (오차의 허용범위를 고려한 수동형 필터의 특성 해석)

  • Kim, Jong-Gyeum;Kim, Il-Jung
    • The Transactions of the Korean Institute of Electrical Engineers P
    • /
    • v.58 no.1
    • /
    • pp.38-43
    • /
    • 2009
  • Reactors are connected with capacitors to passive filter circuits for reducing harmonics caused by power conversion application. This passive filter frequently gets out of order by voltage and current stress. Especially filter reactor has too much voltage harmonics components, its trouble rate is higher than capacitor. In this paper, we analyzed voltage and current of reactor and capacitor used for passive filter by simulation and measurement. If reactor has a tolerance on variation of reactance value, series resonance frequency is different from originally filter design frequency and parallel resonance can be generated at the close point of the former. Because filter absorbs harmonic component of non-linear load, much of harmonic voltage has been impacted on reactor.

A Modified Generalized Chebyshev LPF Design with Improved Stopband (개선된 저지 대역을 갖는 변형된 일반화된 체비셰프 저역 통과 필터 설계)

  • Kim In-Seon;Kim Kwang-Soo;Lim Jong-Sik;Ahn Dal
    • The Journal of Korean Institute of Electromagnetic Engineering and Science
    • /
    • v.16 no.11 s.102
    • /
    • pp.1155-1163
    • /
    • 2005
  • In this paper, we suggest the new method to considerably enlarge stopband without increment of filter sire and loss. The proposed low pass filter looks like outward configuration with the published Modified Generalized Chebyshev (MGC) low pass filter, but the element values completely differ from each other. The published MGC fille, had been considered only the second attenuation pole to reject(or suppress) the harmonic, whereas the stopband of the proposed filter is superior to the published MGC filter because not only the second attenuation pole but also the third harmonic of the first attenuation pole is made use of profitably. We fabricate a low pass filter according to the proposed theory. From the measurement of the fabricated filter, we can confirm that the stopband of the proposed filter is reached above 4 times wider than the conventional Generalized Chebyshev(GC) filter and above 1.7 times wider than the published MGC filter.

Image Enhancement for Sub-Harmonic Phased Array by Removing Surface Wave Interference with Spatial Frequency Filter

  • Park, Choon-Su;Kim, Jun-Woo;Cho, Seung Hyun;Seo, Dae-Cheol
    • Journal of the Korean Society for Nondestructive Testing
    • /
    • v.34 no.3
    • /
    • pp.211-219
    • /
    • 2014
  • Closed cracks are difficult to detect using conventional ultrasonic testing because most incident ultrasound passes completely through these cracks. Nonlinear ultrasound inspection using sub-harmonic frequencies a promising method for detecting closed cracks. To implement this method, a sub-harmonic phased array (PA) is proposed to visualize the length of closed cracks in solids. A sub-harmonic PA generally consists of a single transmitter and an array receiver, which detects sub-harmonic waves generated from closed cracks. The PA images are obtained using the total focusing method (TFM), which (with a transmitter and receiving array) employs a full matrix in the observation region to achieve fine image resolution. In particular, the receiving signals are measured using a laser Doppler vibrometer (LDV) to collect PA images for both fundamental and sub-harmonic frequencies. Oblique incidence, which is used to boost sub-harmonic generation, inevitably produces various surface waves that contaminate the signals measured in the receiving transducer. Surface wave interference often degrades PA images severely, and it becomes difficult to read the closed crack's position from the images. Various methods to prevent or eliminate this interference are possible. In particular, enhancing images with signal processing could be a highly cost-effective method. Because periodic patterns distributed in a PA image are the most frequent interference induced by surface waves, spatial frequency filtering is applicable for removing these waves. Experiments clearly demonstrate that the spatial frequency filter improves PA images.

SIR CPW Bandpass Filter with Folded Feed Structure for Suppressing Spurious Harmonics (고조파 억압을 위한 접힌 피드 구조를 갖는 SIR CPW 대역통과 여파기)

  • 박광선;이창언;천동완;이진택;신철재
    • The Journal of Korean Institute of Electromagnetic Engineering and Science
    • /
    • v.15 no.2
    • /
    • pp.159-164
    • /
    • 2004
  • In this paper, we have proposed the folded feed structure for the spurious harmonic suppression and we have designed the SIR CPW bandpass filter using this feed structure. The characteristic of the proposed feed structure was similar to that of the lowpass filter has wide stopband region and this can be used usefully to the spurious harmonic suppression of the bandpass filter. From the simulation and the measurement result, SIR CPW bandpass filter with folded feed structure has good harmonic suppression characteristics up to 5.8 f$\sub$0/ with -20 dB suppression level.

Harmonic Current Compensation based on Three-phase Three-level Shunt Active Filter using Fuzzy Logic Current Controller

  • Salim, Chennai;Benchouia, M.T.;Golea, A.
    • Journal of Electrical Engineering and Technology
    • /
    • v.6 no.5
    • /
    • pp.595-604
    • /
    • 2011
  • A three-phase three-level shunt active filter controlled by fuzzy logic current controller which can compensate current harmonics generated by nonlinear loads is presented. Three-level inverters and fuzzy controllers have been successfully employed in several power electronic applications these past years. To improve the conventional pwm controller performance, a new control scheme based on fuzzy current controller is adopted for three-level (NPC) shunt active filter. The scheme is designed to improve compensation capability of APF by adjusting the current error using a fuzzy rule. The inverter current reference signals required to compensate harmonic currents use the synchronous reference detection method. This technique is easy to implement and achieves good results. To maintain the dc voltage across capacitor constant and reduce inverter losses, a proportional integral voltage controller is used. The simulation of global system control and power circuits is performed using Matlab-Simulink and SimPowerSystem toolbox. The results obtained in transient and steady states under various operating conditions show the effectiveness of the proposed shunt active filter based on fuzzy current controller compared to the conventional scheme.